Service Manual
Table Of Contents
- Cover
- Table of contents
- Part 1 List of Functions
- Part 2 Specifications
- Part 3 Printed Circuit Board Connector Wiring Diagram
- Part 4 Refrigerant Circuit
- Part 5 Functions and Control
- Part 6 Test Operation and Field Settings
- Part 7 Remote Controller
- Part 8 Troubleshooting
- 1. Troubleshooting with LED
- 2. Service Diagnosis
- 3. Error Codes and Description
- 4. Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series
- 5. Troubleshooting for FFQ Series
- 6. Troubleshooting for Branch Provider (BP) Unit
- 7. Troubleshooting for Outdoor Unit
- 8. Thermistor Resistance/Temperature Characteristics
- 9. Pressure Sensor
- 10. Method of Replacing Inverter’s Power Transistors Modules
- Part 9 Appendix
SiUS181631EA Field Settings
Test Operation and Field Settings 129
The numbers in the No. column represent the number of times to press SET (BS2) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory setting
25
Setting of low noise
level
khkkhhk
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh ∗
Level 3 (outdoor fan with 4 step or lower)
khhhkhh
26
Night-time low noise
operation start setting
khkkhkh
About 20:00
khhhhhk
About 22:00 (factory setting)
khhhhkh
∗
About 24:00
khhhkhh
27
Night-time low noise
operation end setting
khkkhkk
About 6:00
khhhhhk
About 7:00
khhhhkh
About 8:00 (factory setting)
khhhkhh
∗
28
Power transistor
check mode
khkkkhh
OFF
khhhhhk
∗
ON
khhhhkh
29
Capacity precedence
setting
khkkkhk
OFF
khhhhhk
∗
ON
khhhhkh
30 Demand setting 1
khkkkkh
60 % demand
khhhhhk
70 % demand
khhhhkh
∗
80 % demand
khhhkhh
32
Constant demand
setting
kkhhhhh
OFF
khhhhhk
∗
ON
khhhhkh