Branch Provider (BP) Unit Control SiUS181631EA
68 Functions and Control
6. Branch Provider (BP) Unit Control
6.1 Branch Provider (BP) Unit Command Conversion
1.
∆
D (room thermistor temperature
−
target temperature) signals from BP units are
converted to a capacity up/down signal.
∆
D signals from BP units are used as the capacity up/down signal in frequency commands
(excludes during POWERFUL operation).
2. Processing during POWERFUL operation
(1) When POWERFUL command is received from one or more indoor units
(2) Thermostats are not OFF at the indoor units from which POWERFUL commands are issued
When the above conditions are met, the POWERFUL operation is activated, and the
POWERFUL operation signal is sent to the outdoor unit.
∆
D Signal Capacity up/down signal
0 Thermostat OFF
1
Down
2
3
Keep
4
5
Up
6
7
8
9
10
11
12
13
14
15