When there is no signal from the motion sensor in 20 minutes, the microcomputer judges that
nobody is in the room and operates the unit at a temperature shifted from the target
temperature. (Cooling/Dry: 1 ~ 2°C (1.8 ~ 3.6°F) higher, Heating: 2°C (3.6°F) lower, Auto:
according to the operation mode at that time.)
Note: For dry operation, the target temperature is shifted internally. The temperature cannot be set with
the remote controller.
7.12 POWERFUL Operation
Outline In order to exploit the cooling and heating capacity to full extent, the air conditioner can be operated
by increasing the indoor fan rotating speed and the compressor frequency.
Details When POWERFUL button is pressed, the fan speed and target temperature are converted to the
following states for 20 minutes.
A
= 50 ~ 90 rpm (depending on the model)
Ex: POWERFUL operation in cooling
Note: POWERFUL operation cannot be used together with ECONO, COMFORT AIRFLOW or
OUTDOOR UNIT QUIET operation.
Operation mode Fan speed Target temperature
COOL H tap + A rpm 18°C (64.4°F)
DRY Dry rotating speed + A rpm
Lowered by 2 ~ 2.5°C
(3.6 ~ 4.5°F)
HEAT H tap + A rpm 30 ~ 31.5°C (86 ~ 88.7°F)
FAN H tap + A rpm
AUTO Same as cooling/heating in
POWERFUL operation
The target temperature is
kept unchanged.
(R24589)
Target temp.
Fan
A rpm
H tap
Set tap
20 minutes
Lower limit of cooling
temperature
Remote controller registers
20 minutes independently.
POWERFUL
ON
POWERFUL
OFF
Ending condition:
1. Lapse of 20 minutes
2. System operation OFF
3. POWERFUL operation OFF
18˚C (64.4˚F)