Troubleshooting for Outdoor Unit SiUS181631EA
252 Troubleshooting
7.24 Low Pressure Drop due to Refrigerant Shortage or
Electronic Expansion Valve Abnormality
Error Code
U0
Method of Error
Detection
Refrigerant shortage is detected by discharge pipe thermistor and low pressure saturation
temperature.
Error Decision
Conditions
Microcomputer judge and detect if the system is short of refrigerant.
★
The error is not decided while the operation continues.
Supposed
Causes
Refrigerant shortage or refrigerant system clogging (incorrect piping)
Defective low pressure sensor
Defective main PCB (A1P)
Defective thermistor (R3T)