Spec Sheet Heat Pump

Submittal Data Sheet
3.5-Ton DC Ducted Unit
FBQ42PVJURZQ42TAVJU
SYSTEM PERFORMANCE
Indoor Unit Model No. FBQ42PVJU Indoor Unit Name: Sky-Air DC Ducted
Outdoor Unit Model No. RZQ42TAVJU Outdoor Unit Name: Sky-Air 3.5 Ton Heat Pump ODU
Rated Cooling Capacity (Btu/hr): 40,500 Rated Cooling Conditions:
Indoor (°F DB/WB): 80 / 67
Ambient (°F DB/WB): 95 / 75
Sensible Capacity (Btu/hr): 30,500 Rated Piping Length(ft): 25
Max/Min Cooling Capacity (Btu/hr): / Rated Height Difference (ft): 0.00
Cooling Input Power (kW): 3.490 Rated Heating Conditions:
Indoor (°F DB/WB): 70 / 60
Ambient (°F DB/WB): 47 / 43
SEER (Non-Ducted/Ducted): / 16.00
EER (Non-Ducted/Ducted): / 10.10
Rated Heating Capacity (Btu/hr): 47,000
SYSTEM DETAILS
Refrigerant Type: R-410A Cooling Operation Range (°F DB): 23 - 122
Holding Refrigerant Charge (lbs): 7.9 Heating Operation Range (°F WB): -4 - 60
Additional Charge (lb/ft): 0.04 Max. Pipe Length (Vertical) (ft): 98
Pre-charge Piping (Length) (ft): 15 Cooling Range w/Baffle (°F DB): 0 - 122
Max. Pipe Length (Total) (ft): 230 Heating Range w/Baffle (°F WB): -
Max Height Separation (Ind to Ind ft): 0
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056
Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without
incurring any obligations)
Submittal Date: 6/3/2019 8:57:29 AM Page 2 of 4