Service Manual
Table Of Contents
- Cover
- Table of contents
- Part 1 List of Functions
- Part 2 Specifications
- Part 3 Printed Circuit Board Connector Wiring Diagram
- Part 4 Refrigerant Circuit
- Part 5 Functions and Control
- Part 6 Test Operation and Field Settings
- Part 7 Remote Controller
- Part 8 Troubleshooting
- 1. Troubleshooting with LED
- 2. Service Diagnosis
- 3. Error Codes and Description
- 4. Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series
- 5. Troubleshooting for FFQ Series
- 6. Troubleshooting for Branch Provider (BP) Unit
- 7. Troubleshooting for Outdoor Unit
- 8. Thermistor Resistance/Temperature Characteristics
- 9. Pressure Sensor
- 10. Method of Replacing Inverter’s Power Transistors Modules
- Part 9 Appendix
SiUS181631EA Field Settings
Test Operation and Field Settings 147
2.3.2 Overview of the Field Settings
: factory setting
Note: Any function that is not available on the indoor unit is not displayed.
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01 02 03 04 05 06
10
(20)
0
Filter cleaning
sign interval
Longlife
filter
Light
Approx.
2,500
hrs.
Heavy
Approx.
1,250
hrs.
————
2 Remote controller thermistor Enabled
Disabled————
3 Filter cleaning sign DisplayNo display————
12
(22)
0
Optional accessories output
selection (field selection of
output for adaptor for wiring)
Compressor —
Operation
output
Error output
Outdoor air
intake
Presence
sensor
13
(23)
0
High air outlet velocity (for high
ceiling applications)
≤
2.7 m
(
≤
8-7/8 ft)
2.7 ~ 3.0 m
(8-7/8~9-13/16 ft)
3.0 ~ 3.5 m
(9-13/16~11-1/2 ft)
———
1
Selection of airflow direction
(setting for when a blocking
pad kit has been installed)
4-way flow 3-way flow 2-way flow — — —
4 Airflow direction range setting Upper
Normal Lower — — —
15
(25)
3
Drain pump operation with
humidifying
Not equipped
Equipped — — — —