Service Manual

SiUS181631EA Method of Replacing Inverter’s Power Transistors Modules
Troubleshooting 271
Power module checking
When using the digital type of multimeter, make measurement in diode check mode.
There needs to be none of each value variation.
The following abnormalities are also doubted besides the PCB abnormality.
h
Defective compressor (ground fault, ground leakage)
h
Defective fan motor (ground leakage)
Multimeter terminal Criterion Remark
+–
C+ U Not less than 0.3 V
(including
)
It may take time to
determine the voltage due
to capacitor charge or else.
V
W
U C– Not less than 0.3 V
(including
)
V
W
U C+ 0.3 ~ 0.7 V
(including
)
V
W
C– U 0.3 ~ 0.7 V
(including
)
V
W