Specifications

SiBE28-805 Field Setting
Test Operation 89
(10) Auto Restart after Power Failure Reset
For the air conditioners with no setting for the function (same as factory setting), the units will be
left in the stop condition when the power supply is reset automatically after power failure reset
or the main power supply is turned on again after once turned off. However, for the air
conditioners with the setting, the units may start automatically after power failure reset or the
main power supply turned on again (return to the same operation condition as that of before
power failure).
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power
failure reset”, utmost care should be paid for the occurrence of the following situation.
(11) Airflow when Cooling Thermostat is OFF
This is used to set airflow to "LL airflow" when cooling thermostat is OFF.
(12) Setting of Normal Airflow
Make the following setting according to the ceiling height. The setting position No. is set to “01”
at the factory.
In the Case of FMCQ50~71 (All round outlet)
In the Case of FMCQ100~125 (All round outlet)
In the Case of FMCQ50~71 (*
2
4-Way, 3-Way, 2-Way Outlets)
Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
Mode No. First Code No. Second Code No. Contents
12 (22) 6
01 LL airflow
02 Preset airflow
Mode
No.
First
code
No.
Second
code
No.
Setting Ceiling height (m)
13 (23) 0
01
Standard • All
round outlet
2.7
02 High Ceiling (1) 2.7-3
03 Higher Ceiling (2) 3-3.5
Mode
No.
First
code
No.
Second
code
No.
Setting Ceiling height (m)
13 (23) 0
01
Standard • All
round outlet
3.2
02 High Ceiling (1) 3.2-3.6
03 Higher Ceiling (2) 3.6-4.2
Mode
No.
First
code
No.
Second
code
No.
Setting
Ceiling height
4-way Outlets 3-way Outlets 2-way Outlets
13 (23) 0
01 Standard (N) Lower than 3.1 m Lower than 3.0 m Lower than 3.5 m
02 High Ceiling (H) Lower than 3.4 m Lower than 3.3 m Lower than 3.8 m
03 Higher Ceiling (S) Lower than 4.0 m Lower than 3.5 m