Specifications

Field Setting SiBE28-805
90 Test Operation
In the Case of FMCQ100~125 (*
2
4-Way, 3-Way, 2-Way Outlets)
*1 Mode No.” setting is done in a batch for the group. To make or confirm settings for an
individual unit, set the internal mode number in parentheses.
*2 The figure of the ceiling height is for the all round outlet. For the settings for four-direction
(part of corner closed off), three-direction and two-direction outlets, see the installation
manual and technical guide supplied with the separately sold closure material kit.
(13) Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to “01.”
Setting Table
(14) Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Setting Table
Some indoor unit models are not equipped with draft prevention (upward) function.
(15) Setting of the Static Pressure Selection
(16) Humidification when Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction temperature is 20ºC or
above and turns OFF the humidifier if suction temperature is 18ºC or below when the heating
thermostat is OFF.
Mode
No.
First
code
No.
Second
code
No.
Setting
Ceiling height
4-way Outlets 3-way Outlets 2-way Outlets
13 (23) 0
01 Standard (N) Lower than 3.4 m Lower than 3.6 m Lower than 4.2 m
02 High Ceiling (H) Lower than 3.9 m Lower than 4.0 m Lower than 4.2 m
03 Higher Ceiling (S) Lower than 4.5 m Lower than 4.2 m
Mode No. First Code No.
Second Code
No.
Setting
13 (23) 1
01 F : 4-direction airflow
02 T : 3-direction airflow
03 W : 2-direction airflow
Mode No. First Code No. Second Code No. Setting
13 (23) 4
01
Upward (Draft
prevention)
02 Standard
03
Downward (Ceiling
soiling prevention)
Model No. First Code No. Second Code No. External static pressure
13 (23) 6
01 Standard
02 High static pressure
03 Low static pressure
Mode No. First Code No. Second Code No. Setting
15 (25) 1
01
02 Setting of humidifier