Specifications

SiBE28-805 Field Setting
Test Operation 105
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory set
22
Night-time low noise
setting
khkhkkh
OFF
khhhhhh
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh
Level 3 (outdoor fan with 4 step or lower)
khhhhkk
24
ENECUT test
operation (Domestic
Japan only)
khkkhhh
ENECUT output OFF
khhhhhk
ENECUT output forced ON
khhhhkh
25 Low noise setting
khkkhhk
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh
Level 3 (outdoor fan with 4 step or lower)
khhhkhh
26
Night-time low noise
operation start
setting
khkkhkh
About 20:00
khhhhhk
About 22:00 (factory setting)
khhhhkh
About 24:00
khhhkhh
27
Night-time low noise
operation end
setting
khkkhkk
About 6:00
khhhhhk
About 7:00
khhhhkh
About 8:00 (factory setting)
khhhkhh
28
Power transistor
check mode
khkkkhh
OFF
khhhhhk
ON
khhhhkh
29
Capacity
precedence setting
khkkkhk
OFF
khhhhhk
ON
khhhhkh
30 Demand setting 1
khkkkkh
60 % demand
khhhhhk
70 % demand
khhhhkh
80 % demand
khhhkhh
32
Normal demand
setting
kkhhhhh
OFF
khhhhhk
ON
khhhhkh
35
Setting of difference
in elevation for the
outdoor unit
kkhhhkk
Normal
khhhhhh
65 m or less
khhhkkh
90 m or less
khhhkkk