Specifications

SiBE28-805 Model Selection
General Information 5
4. Model Selection
Connectable Indoor Unit
Indoor unit capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
The total capacity of connected indoor units must be within a range of 50 to 100% of the
rated capacity of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor
units. Select models so the total capacity of connected indoor units conforms to the
specification.
Type Model Name Power Supply
Ceiling Mounted
Cassette Type
(Multi Flow)
FMCQ 50A 60A 71A 100A 125A VE
Ceiling Mounted
Built-In Type
FMDQ 50A 60A 71A 100A 125A V3
New refrigerant model code P50 type P60 type P71 type P100 type P125 type
Selecting model capacity 5.0~5.6kW 6.0~7.0kW 7.1~8.0kW 10.0~11.2kW 12.5~14.0kW
Equivalent output 2.0HP 2.3HP 2.5HP 4HP 5HP