Specifications

Specifications SiBE28-805
10 Specifications
ELECTRICAL SPECIFICATIONS CMSQ200A7W1B CMSQ250A7W1B
Power Supply
Name W1
Phase 3N~
Frequency Hz 50
Voltage V 400
Current
Nominal Running
Current (RLA)
Cooling A 9.53 9.73
Heating A 8.38 9.86
Minimum Ssc Value kVa 1,218
Minimum Circuit Amps (MCA) A 11.9 18.5
Maximum Fuse Amps (MFA) A 16 25
Total Overcurrent Amps (TOCA) A 15.6 16.5
Full Load Amps (FLA) A 0.4 0.7
Voltage Range
Minimum V 360
Maximum V 440
Wiring Connections
For Power Supply
Quantity 5
Remark Earth Wire Include
For connection with
Indoor
Quantity 2
Remark F1 - F2
Power Supply Intake Both Indoor and Outdoor Unit
Notes
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage
circuit breaker)
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
RLA is based on following conditions : indoor temperature : 27°CDB/19°CWB , outdoor
temperature : 35°CDB
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit
terminal is not below or above listed range limits