Specifications

Test Operation SiBE28-805
76 Test Operation
Setting the mode
The set mode can be changed with the BS1 MODE button according to the following procedure:
For setting mode 1: Press the BS1 MODE button once, the H1P LED is off
h
.
For setting mode 2: Press the BS1 MODE button for 5 seconds, the H1P LED is on
k
.
If the H1P LED is blinking
l
and the BS1 MODE button is pushed once, the setting mode will
change to setting mode 1.
Note:
If you get confused in the middle of the setting process, push the BS1 MODE button. Then it
returns to setting mode 1 (H1P LED is off).
Setting mode 1
The H1P LED is off (COOL/HEAT selection setting).
Setting procedure
1. Push the BS2 SET button and adjust the LED indication to either one of the possible settings
as shown below in the field marked :
2. Push the BS3 RETURN button and the setting is defined.
The H1P LED is on.
Setting procedure
1. Push the BS2 SET button according to the required function (A~H). The LED indication that
matches the required function is shown below in the field marked :
Possible functions
A additional refrigerant charging operation.
B refrigerant recovery operation/vacuuming operation.
C setting of high static pressure.
D automatic low noise operation setting at nighttime.
E low noise operation level setting (L.N.O.P) via the external control adaptor.
F power consumption limitation setting (DEMAND) via the external control adaptor.
G enabling function of the low noise operation level setting
(L.N.O.P) and/or power consumption limitation setting
(DEMAND) via the external control adaptor (DTA104A61/62).
G check operation (without initial refrigerant decision)
2. When the BS3 RETURN button is pushed, the current setting is defined.
3. Push the BS2 SET button according to the required setting possibility as shown below in the
field marked .
3.1Possible settings for function A, B, C, G and H are ON (ON) or OFF (OFF).
In case of COOL/HEAT setting by each individual outdoor unit circuit.
H1P H2P H3P H4P H5P H6P H7P
h
h l h h h h
Setting mode 2
A
H1P H2P H3P H4P H5P H6P H7P
k h k h k h h
B
k h k h k h k
C
k h k h h k h
D
k h k h k k h
E
k
h k k h h k
F
k h k k k k h
G
k h h k k h h
H
k h h h h k k
H1P H2P H3P H4P H5P H6P H7P
ON
khhhh
l h
OFF
(a)
khhhhh l
(a) This setting = factory setting