Specifications
SiBE28-805 Field Setting
Test Operation 85
3.1.4 Setting Contents and Code No. – Indoor unit
Notes : 1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Marked are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. “88” may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
6. If the setting mode to “Equipped”, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
7. If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for
group connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-
2-03 have priority.
8. Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Indoor
unit
settings
Mode
No.
Note 2
Setting
Switch
No.
Setting Contents
Second Code No.(Note 3)
Details
No.
01 02 03 04
10
(20)
0
Filter contamination heavy/
light (Setting for display
time to clean air filter)
(Sets display time to clean
air filter to half when there
is heavy filter
contamination.)
Super
long life
filter
Light
Approx.
10,000 hrs.
Heavy
Approx.
5,000 hrs.
——
(1)
Long life filter
Approx.
2,500 hrs.
Approx.
1,250 hrs.
Standard filter
Approx.
200 hrs.
Approx.
100 hrs.
1 Long life filter type Long life filter
Super long life
filter
——(2)
2
Thermostat sensor in remote controller
Use No use — — (3)
3
Display time to clean air filter calculation
(Set when filter sign is not to be displayed.)
Display No display — — (4)
5
Information to i-Manager, i-Touch
Controller
Only unit sensor value
(or remote sensor value
if installed).
Sensor value as
set by 10-2-0X
or 10-6-0X.
———
6 Thermostat sensor in group control
Use unit sensor
only (or remote
sensor if
installed).
(See note 7)
Use both the unit
senor (or remote
sensor if installed)
AND the remote
controller sensor.
(See note 4+5+6)
———
12
(22)
0
Optional accessories output selection (field
selection of output for adaptor for wiring)
Indoor unit turned
ON by thermostat
—
Operation
output
Malfunction
output
(5)
1
ON/OFF input from outside (Set when ON/
OFF is to be controlled from outside.)
Forced OFF ON/OFF control
External protection
device input
—(6)
2
Thermostat differential changeover
(Set when remote sensor is to be used.)
1°C 0.5°C — — (7)
3 OFF by thermostat fan speed LL Set fan speed
OFF (See note 8)
—(8)
4
Automatic mode differential
(automatic temperature differential
setting for system heat recovery
series cool/heat)
01:0 02:1 03:2 04:3 05:4 06:5 07:6 08:7 (9)
5 Power failure automatic reset Not equipped Equipped — — (10)
6
Airflow When Cooling Thermostat is OFF
LL airflow Preset airflow — — (11)
9
Fixed cool/heat master
Disabled Enabled — — —
13
(23)
0
High air outlet velocity
(Set when installed in place with
ceiling higher than 2.7 m.)
N H S — (12)
1
Selection of airflow direction (Set when a
blocking pad kit has been installed.)
F (4 directions) T (3 directions) W (2 directions) — (13)
4 Field set airflow position setting Draft prevention Standard
Ceiling Soiling prevention
— (14)
6
Setting the external static pressure
(To be set in function of the
connected duct resistance)
Normal
High static
pressure
Low static
pressure
— (15)
15
(25)
1 Thermostat OFF excess humidity Not equipped Equipped — — (16)
2
Direct duct connection
(when the indoor unit and heat
reclaim ventilation unit are
connected by duct directly.) ∗Note 6
Not equipped Equipped — — (17)
3
Drain pump humidifier interlock selection
Not equipped Equipped — — (18)
5
Field set selection for individual
ventilation setting by remote controller
Not equipped Equipped — — (19)