Spec Sheet

Daikin North America LLC 5151 San Felipe, Suite 500 Houston, TX 77056
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without
notice and without incurring any obligations)
Submittal Creation Date: June 2017 Page 1 of 4
Performance
Cooling (Btu/hr)
Rated (Min/Max)
21,200 (5,500 / 24,000)
Sensible @ AHRI
15,760
Moisture Removal gal/h
1.2
Operating Range
50°F 115°F
Rated Cooling Conditions:
Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
Submittal Data Sheet
FTK24NMVJU / RK24NMVJU
Efficiency
Cooling
SEER
18
EER
12.5
Electrical
208/60/1
230/60/1
System MCA
18.3
18.3
System MFA
20
20
Compressor RLA
12.0
12.0
Outdoor fan motor FLA
.38
.38
Outdoor fan motor W
58
58
Indoor fan motor FLA
.30
.30
Indoor fan motor W
46
46
MFA: Max. fuse amps MCA: Min. circuit amps (A) FLA: Full load amps (A)
RLA: Rated load amps (A) W: Fan motor rated output (W)
Piping
Liquid (in)
1/4
Gas (in)
5/8
Drain (in)
5/8
Max. Interunit Piping Length (ft)
98.4
Max. Interunit Height Difference (ft)
65.625
Chargeless (ft)
32.8
Additional Charge of Refrigerant (oz/ft)
.21
Indoor Specifications
Airflow Rate (cfm)
Cooling
H
M
713
579
L
SL
512
403
Sound (dBA)
H / M / L / SL
53 / 45 / 39 / 34
Dimensions (H × W × D) (in)
11-5/8 × 39 × 10-3/8
Weight (Lbs)
27
Outdoor Specifications
Compressor
Hermetically Sealed Swing Type
Refrigerant
R-410A
Refrigerant Oil
PVE (FVC50K)
Airflow Rate (cfm)
Cooling
H
2,101
SL
1,762
Sound Power Level (dBA)
55
Dimensions (H × W × D) (in)
28-15/16 × 34-1/4 × 12-5/8
Weight (Lbs)
108
Job Name:
Tag#
Complete warranty details available from your local dealer or at
www.daikincomfort.com. To receive the 12-Year Parts Limited
Warranty, online registration must be completed within 60 days of
installation. Online registration is not required in California or Quebec.
If product is installed in a commercial application, limited warranty
period is 5 years.