EDUS041701 Split Type Air Conditioners - Cooling Only / Heat Pump FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Cooling Only Heat Pump FTX30NVJU FTX36NVJU FTX30NVJU FTX36NVJU RK30NMVJU RK36NMVJU RX30NMVJU RX36NMVJU 1. Power Supply ..............................................................................................3 2. Functions..................................................................................................... 4 3. Specifications ..............................................................................................5 3.
EDUS041701 13.Optional Accessories ................................................................................83 13.1 13.2 13.3 13.4 13.5 Option List .................................................................................................. 83 Wired Remote Controller..................................................... 84 Wireless LAN Connection Adaptor.................................... 98 Wiring Adaptor for Timer Clock / Remote Controller ....
EDUS041701 Power Supply 1.
Functions EDUS041701 Comfortable Airflow Comfort Control Operation Lifestyle Convenience z Refer to P.
EDUS041701 Specifications 3. Specifications 3.1 Cooling Only 60 Hz, 208 - 230 V Indoor Unit Outdoor Unit Rated Capacity Min. ~ Max. Running Current (Rated) Rated Power Consumption Min. ~ Max. Power Factor (Rated) SEER / HSPF COP (Rated) EER (Rated) Liquid Piping Connections Gas Drain Heat Insulation Max. Interunit Piping Length Max.
Specifications 3.2 EDUS041701 Heat Pump 60 Hz, 208 - 230 V Indoor Unit Model Capacity Outdoor Unit Rated Btu/h Min. ~ Max. Btu/h Running Current (Rated) Rated Power Consumption Min. ~ Max. Power Factor (Rated) SEER / HSPF COP (Rated) EER (Rated) Liquid Piping Connections Gas Drain Heat Insulation Max. Interunit Piping Length Max.
EDUS041701 Dimensions 4. Dimensions 4.1 Indoor Unit FTX30/36NVJU THE MARK (→) SHOWS PIPING DIRECTION AIRFLOW (INDOOR) 1-3/16 (30mm) MIN (SPACE FOR PERFORMANCE) 47-1/4 (1200mm) REAR LEFT RIGHT ( ) INCLUDING MOUNTING PLATE 10-1/4 (261mm) FRONT GRILLE FIXED SCREWS (INSIDE) 1-15/16 (50mm) MIN (SPACE FOR MAINTENANCE) NAME PLATE 1-15/16 (50mm) MIN (SPACE FOR MAINTENANCE) REQUIRED SPACE TERMINAL BLOCK WITH GROUND TERMINAL INTELLIGENT EYE SENSOR SIGNAL RECEIVER 7-7/16 (188.7mm) 2-5/16 (58.
Wiring Diagrams EDUS041701 5. Wiring Diagrams 5.1 Indoor Unit FTX30/36NVJU WIRING DIAGRAM 1 PCB3 S49 1 LED1 H1P LED2 H2P LED3 H3P 9 S46 1 BLK BLK BLK BLK BLK BLK BLK BLK BLK PCB1 X1M FU1 F1U H1 3.15A ~ C102 V1 - MR10 H2 3 CAUTION FU2 F2U RTH1 R1T S1 7 BZ RED 3.
EDUS041701 Piping Diagrams 6. Piping Diagrams 6.1 Indoor Unit FTX30/36NVJU INDOOR UNIT 5/16 CuT DISTRIBUTOR HEAT EXCHANGER FIELD PIPING 1/4 CuT CROSS FLOW FAN THERMISTOR ON HEAT EXCH.
Piping Diagrams EDUS041701 6.2 Outdoor Unit 6.2.
EDUS041701 Capacity Tables 7. Capacity Tables 7.1 Cooling Only FTX30NVJU + RK30NMVJU AFR 25.22 BF 0.34 60 Hz, 208 V Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) EWB EDB 10 20 °C °C TC SHC PI TC SHC PI TC SHC 30 PI TC SHC 35 PI TC SHC 40 PI TC SHC 46 PI 14.0 16.0 20.0 22.0 8.10 9.95 5.71 6.38 1.83 1.95 8.10 9.83 5.71 6.31 2.39 2.46 8.10 8.97 5.71 5.86 2.92 2.93 8.10 8.55 5.71 5.64 3.15 3.17 7.39 7.79 5.33 5.27 3.13 3.13 5.92 6.33 4.59 4.
Capacity Tables EDUS041701 Symbols: Notes: AFR : Airflow rate BF : Bypass factor (m /min.) EWB : Entering wet bulb temp. (°C) / (°F) EDB : Entering dry bulb temp. (°C) / (°F) TC : Total capacity (kW) / (kBtu/h) SHC : Sensible heat capacity (kW) / (kBtu/h) PI : Power input (kW) 3 1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the above tables.
EDUS041701 Capacity Tables FTX36NVJU + RK36NMVJU AFR 25.92 BF 0.34 60 Hz, 208 V Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) EWB EDB 10 20 °C °C TC SHC PI TC SHC PI TC SHC 30 PI TC SHC 35 PI TC SHC 40 PI TC SHC 46 PI 14.0 20.0 8.33 5.87 1.99 8.33 5.87 2.62 8.33 5.87 3.16 8.33 5.87 3.42 7.55 5.45 3.14 6.02 4.69 2.64 16.0 22.0 10.23 6.55 2.10 10.23 6.55 2.66 9.56 6.20 3.18 9.10 5.96 3.44 7.98 5.40 3.14 6.45 4.68 2.
Capacity Tables EDUS041701 Symbols: Notes: AFR : Airflow rate BF : Bypass factor (m /min.) EWB : Entering wet bulb temp. (°C) / (°F) EDB : Entering dry bulb temp. (°C) / (°F) TC : Total capacity (kW) / (kBtu/h) SHC : Sensible heat capacity (kW) / (kBtu/h) PI : Power input (kW) 3 1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the above tables.
EDUS041701 7.2 Capacity Tables Heat Pump FTX30NVJU + RX30NMVJU 60 Hz, 208 V Cooling AFR 25.22 BF 0.34 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) EWB EDB 10 20 °C °C TC SHC PI TC SHC PI TC SHC 30 PI TC SHC 35 PI TC SHC 40 PI TC SHC 46 PI 14.0 20.0 8.10 5.71 1.83 8.10 5.71 2.39 8.10 5.71 2.92 8.10 5.71 3.15 7.39 5.33 3.13 5.92 4.59 2.64 16.0 22.0 9.95 6.38 1.95 9.83 6.31 2.46 8.97 5.86 2.93 8.55 5.64 3.17 7.79 5.27 3.
Capacity Tables EDUS041701 60 Hz, 230 V Cooling AFR 25.22 BF 0.34 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) EWB EDB 10 20 °C °C TC SHC PI TC SHC PI TC SHC 30 PI TC SHC 35 PI TC SHC 40 PI TC SHC 46 PI 14.0 20.0 8.10 5.71 1.83 8.10 5.71 2.39 8.10 5.71 2.92 8.10 5.71 3.15 7.70 5.49 3.39 6.26 4.76 2.92 16.0 22.0 9.95 6.38 1.95 9.83 6.31 2.46 8.97 5.86 2.93 8.55 5.64 3.17 8.12 5.43 3.40 6.67 4.74 2.92 18.0 25.0 11.
EDUS041701 Capacity Tables Symbols: Notes: AFR : Airflow rate BF : Bypass factor (m /min.) EWB : Entering wet bulb temp. (°C) / (°F) EDB : Entering dry bulb temp. (°C) / (°F) TC : Total capacity (kW) / (kBtu/h) SHC : Sensible heat capacity (kW) / (kBtu/h) PI : Power input (kW) 3 1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the above tables.
Capacity Tables EDUS041701 FTX36NVJU + RX36NMVJU 60 Hz, 208 V Cooling AFR 25.92 BF 0.34 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) EWB EDB 10 20 °C °C TC SHC PI TC SHC PI TC SHC 30 PI TC SHC 35 PI TC SHC 40 PI TC SHC 46 PI 14.0 20.0 8.33 5.87 1.99 8.33 5.87 2.62 8.33 5.87 3.16 8.33 5.87 3.42 7.55 5.45 3.14 6.02 4.69 2.64 16.0 22.0 10.23 6.55 2.10 10.23 6.55 2.66 9.56 6.20 3.18 9.10 5.96 3.44 7.98 5.40 3.14 6.45 4.
EDUS041701 Capacity Tables 60 Hz, 230 V Cooling AFR 25.92 BF 0.34 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) EWB EDB 10 20 °C °C TC SHC PI TC SHC PI TC SHC 30 PI TC SHC 35 PI TC SHC 40 PI TC SHC 46 PI 14.0 20.0 8.33 5.87 2.21 8.33 5.87 2.90 8.33 5.87 3.46 8.33 5.87 3.74 7.74 5.55 3.43 6.11 4.73 2.89 16.0 22.0 10.23 6.55 2.30 10.23 6.55 2.92 9.85 6.35 3.48 9.38 6.11 3.75 8.18 5.50 3.43 6.55 4.72 2.89 18.0 25.0 12.
Capacity Tables EDUS041701 Symbols: Notes: AFR : Airflow rate BF : Bypass factor (m /min.) EWB : Entering wet bulb temp. (°C) / (°F) EDB : Entering dry bulb temp. (°C) / (°F) TC : Total capacity (kW) / (kBtu/h) SHC : Sensible heat capacity (kW) / (kBtu/h) PI : Power input (kW) 3 1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the above tables.
EDUS041701 7.3 Capacity Tables Capacity Correction Factor by the Length of Refrigerant Piping (Reference) The cooling capacity and the heating capacity of the unit have to be corrected in accordance with the length of refrigerant piping — the distance between the indoor unit and the outdoor unit. <— line : cooling capacity> <--- line : heating capacity> (R-410A) (%) Capacity correction factor 100 90 Range of the refrigerant additional charge 80 16.4 5 32.8 10 49.2 15 65.6 20 82.0 25 98.
Operation Limit EDUS041701 8.
EDUS041701 Sound Level 9. Sound Level 9.1 Measuring Location Indoor Unit Outdoor 3.3 ft (1 m) 2.6 ft (0.8 m) 3.3 ft (1 m) MICROPHONE MICROPHONE Notes: 9.2 1. Operation sound is measured in an anechoic chamber. 2. The operation sound measuring method is based on JIS standard. Indoor Unit FTX30NVJU COOLING 70 NC-70 OVER ALL ( dB ) NC-60 60Hz 208/230V (H) 60Hz 208/230V (L) 53 40 SCALE 60 A ( B.G.
Sound Level 9.3 Outdoor Unit 9.3.1 Cooling Only EDUS041701 RK30NMVJU COOLING OCTAVE BAND SOUND PRESSURE LEVEL dB(0dB=0.0002µ bar) 60 SCALE 208-230V 60Hz A 56 NC-60 ( B.G.N IS ALREADY RECTIFIED ) 50 NC-50 OPERATING CONDITIONS 208-230V 60Hz POWER SOURCE 40 JIS STANDARD NC-40 30 Cooling NC-30 20 APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE 63 9.3.
EDUS041701 Electric Characteristics 10. Electric Characteristics Unit Combination Indoor Unit Outdoor Unit FTX30NVJU RK30NMVJU FTX36NVJU RK36NMVJU FTX30NVJU RX30NMVJU FTX36NVJU RX36NMVJU Power Supply Compressor OFM IFM Hz - Volts Voltage Range MCA MFA RLA W FLA W FLA 60 - 208 MAX. 60 Hz, 253 V MIN. 60 Hz, 187 V 17 20 16.25 93 0.62 64 0.37 MAX. 60 Hz, 253 V MIN. 60 Hz, 187 V 17 20 16.25 123 0.83 64 0.37 MAX. 60 Hz, 253 V MIN. 60 Hz, 187 V 19.8 20 18.25 93 0.
Installation Manual EDUS041701 11. Installation Manual 11.
EDUS041701 Split Type Air Conditioners FTX-N Series Installation Manual 27
Installation Manual 28 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Installation Manual 29
Installation Manual 30 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Installation Manual 31
Installation Manual 32 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Installation Manual 33
Installation Manual 34 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Installation Manual 3P457790-1 Split Type Air Conditioners FTX-N Series 35
Installation Manual EDUS041701 11.
EDUS041701 Split Type Air Conditioners FTX-N Series Installation Manual 37
Installation Manual 38 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Installation Manual 39
Installation Manual 40 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Installation Manual 41
Installation Manual 42 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Installation Manual 43
Installation Manual 44 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Installation Manual 45
Installation Manual 46 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Installation Manual 3P457793-1 Split Type Air Conditioners FTX-N Series 47
Operation Manual EDUS041701 12.
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 49
Operation Manual 50 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 51
Operation Manual 52 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 53
Operation Manual 54 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 55
Operation Manual 56 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 57
Operation Manual 58 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 59
Operation Manual 60 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 61
Operation Manual 62 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 63
Operation Manual 64 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 65
Operation Manual 66 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 67
Operation Manual 68 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 69
Operation Manual 70 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 71
Operation Manual 72 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 73
Operation Manual 74 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 75
Operation Manual 76 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 77
Operation Manual 78 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 79
Operation Manual 80 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Operation Manual 81
Operation Manual EDUS041701 3P457796-1 82 Split Type Air Conditioners FTX-N Series
EDUS041701 Optional Accessories 13. Optional Accessories 13.1 Option List 13.1.1 Indoor Unit Option Name 1 Notes: Model Name Wired remote controller ★1 BRC944B2 Length 9.8 ft (3 m) BRCW901A03 Length 26.
Optional Accessories EDUS041701 13.2 Wired Remote Controller 13.2.1 Installation Manual CAUTION 1. No switch box or staple is supplied. Prepare them locally. 2. No remote controller cord is supplied. Prepare the optional remote controller cord 4 wire. 3. Be sure to turn off the power to any apparatus connected prior to mounting. 4. Prior to mounting equipment, touch something metallic such as a doorknob to remove static electricity from your body.
EDUS041701 Optional Accessories 2. Securing the remote control adapter Double-face adhesive tape Remove the upper case of the remote control adapter and secure the lower case assembly. Wood screws (φ3.5mm x 16mm) (Mounting with supplied double-face adhesive tape) (Mounting with supplied wood screws) 3.
Optional Accessories EDUS041701 13.2.2 Operation Manual Controller Commands and their Corresponding Functions Run indicator lamp (green) ON/OFF button Display Press to start the system. Press again to stop the system. Displays the operating conditions. Timer select button Mode select button Selects one of the following: ONE TIME timer ON DAILY timer ON TIMER OFF Selects an operation mode. ( page 7) Swing button ( page 9) Airflow rate button Adjusts the airflow rate.
EDUS041701 Optional Accessories Preparation before Operation Checking the power If nothing appears on the remote controller's display, turn on the circuit breaker. Setting the current time 1 Press . The current time starts blinking. lights up. 2 2 Press and set the current time. 1 ·3 Hold the button down to rapidly advance the time. 3 Press . blinks. (This completes the current time setting) The clock's accuracy is ±30 seconds per month.
Optional Accessories EDUS041701 Preparation before Operation Setting Temperature Indication change Temperature indication can be changed between Celsius and Fahrenheit before use. To change from Celsius temperature indication to Fahrenheit one 1 Press and hold down at the same time for 5 seconds while the Celsius temperature is indicated.
EDUS041701 Optional Accessories Automatic · DRY · Cooling · Heating Operation Select your desired operation mode. Once preset, the system can get restarted in the same operation mode. 1 Run indicator lamp (green) to select your desired Press operation mode. Each time the button is pressed, the mode changes as follows. (Automatic) (DRY) (Heating) (Cooling) 2 Heat pump model 1 (DRY) (Cooling) Cooling only model The system does not have the FAN mode. 2 Press .
Optional Accessories EDUS041701 To adjust the temperature and airflow rate: Operation mode Setting to be adjusted Automatic Cooling Heating DRY Temperature is adjustable. Temperature cannot be adjusted. Recommended temperature (Temperature) Cooling : 26˚C-28˚C (79˚F~82˚F) Heating : 20˚C-22˚C (68˚F~72˚F) Five levels of airflow rate setting from " " to " " plus " " are available. (Airflow rate) Airflow rate cannot be adjusted.
EDUS041701 Optional Accessories Adjusting Airflow Direction Adjust the airflow direction for maximum comfort. To adjust the Airflow Direction 1 Press during operation. Each time the button is pressed, the airflow direction louvers change their movement. 1 Wall Mounted Types (without horizontal swing function) Swing Airflow direction louvers stop The horizontal airflow direction louvers move up and down. The louvers stop just when the button is pressed.
Optional Accessories EDUS041701 Wall Mounted Type (with horizontal swing function) Swing horizontally Swing vertically Airflow direction louvers stop The horizontal airflow direction louvers move up and down. The horizontal airflow direction louvers stop just when the button is pressed. Then the vertical ones start moving right and left. The vertical airflow direction louvers stop just when the button is pressed. The vertical and horizontal louvers cannot move at the same time.
EDUS041701 Optional Accessories Timer Operation The Timer Operation feature automatically turns off operation when you go to sleep and turns it back on when you wake up. Use the DAILY Timer mode on weekdays, and the ONE TIME timer mode on weekends. To select the ONE TIME timer mode: 1 Press to select the ONE TIME timer mode. Each time the button is pressed, the modes change as follows.
Optional Accessories EDUS041701 ONE TIME timer Once the timer has been activated and then deactivated, it is in the OFF mode. The ON or OFF timers can be programmed. 1 Press to select the ONE TIME timer. 4 Press . blinks. ONE TIME light up. 2 Press 5 Press . When the OFF timer is not used, save the setting as . blinks. 3 Press to make the OFF timer setting. to make the ON timer setting. 6 Press . (The ONE TIME timer is now programmed.
EDUS041701 Optional Accessories Timer Operation To select the DAILY timer mode: Timers 1 Press 1 2 Two pairs of ON and OFF time settings can be programmed. to select the DAILY timer mode. Each time the button is pressed, the modes change as follows. ONE TIME timer ON time 24-hour timer display The settings of timers 1 and 2 can be seen at a glance. OFF time DAILY timer TIMER OFF The timer lamp lights up.
Optional Accessories EDUS041701 DAILY timer After programming, the system starts and stops each day at the preset times. Two pairs of time settings can be programmed. (Example: 8:00 ~ 10:00, and 18:00 ~ 23:00) DAILY timer indication appears. 1 2 lights up. to select the DAILY timer. Press Make the ON and OFF time settings. Take the steps from to . Program example: 8:00 ~ 10:00, and 18:00 ~ 23:00 Procedure Press Press to make the timer setting.
EDUS041701 Optional Accessories Cleaning Cleaning the remote controller Wipe it clean with soft, dry cloth. Do not use any water hotter than 40˚C (104˚F), or v olatile liquids such as benzine, gasoline and thinner, polishing powder, or anything hard such as a scrub brush. When the unit is not used for a long time 1 On a sunny day, keep the system running for half a day in the FAN mode to dry it up inside. FAN mode 3 2 1 1 Press mode. 2 to adjust the set Press temperature to 32˚C (90˚F).
Optional Accessories EDUS041701 13.
EDUS041701 Split Type Air Conditioners FTX-N Series Optional Accessories 99
Optional Accessories 100 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Optional Accessories 101
Optional Accessories 102 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Optional Accessories 103
Optional Accessories 104 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Optional Accessories 3P427537-1A Split Type Air Conditioners FTX-N Series 105
Optional Accessories EDUS041701 13.
EDUS041701 Split Type Air Conditioners FTX-N Series Optional Accessories 107
Optional Accessories 108 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Optional Accessories 3P248024-2 Split Type Air Conditioners FTX-N Series 109
Optional Accessories EDUS041701 13.
EDUS041701 Optional Accessories 3P248024-1E Split Type Air Conditioners FTX-N Series 111
Optional Accessories EDUS041701 3P248024-3D 112 Split Type Air Conditioners FTX-N Series
EDUS041701 Optional Accessories 13.
Optional Accessories EDUS041701 3P398171-1 114 Split Type Air Conditioners FTX-N Series
EDUS041701 Optional Accessories 13.
Optional Accessories EDUS041701 13.
EDUS041701 Split Type Air Conditioners FTX-N Series Optional Accessories 117
Optional Accessories 118 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Split Type Air Conditioners FTX-N Series Optional Accessories 119
Optional Accessories 120 EDUS041701 Split Type Air Conditioners FTX-N Series
EDUS041701 Optional Accessories 3P421082-1C Split Type Air Conditioners FTX-N Series 121
Optional Accessories EDUS041701 13.
EDUS041701 Optional Accessories 3P436071-1 Split Type Air Conditioners FTX-N Series 123
Optional Accessories EDUS041701 13.
EDUS041701 Optional Accessories 3P436072-1 Split Type Air Conditioners FTX-N Series 125
Optional Accessories EDUS041701 13.
EDUS041701 Optional Accessories 3P436073-1 Split Type Air Conditioners FTX-N Series 127
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories.