EDUS041701 Electric Characteristics
Split Type Air Conditioners FTX-N Series 25
10.Electric Characteristics
3D108105
Unit Combination Power Supply Compressor OFM IFM
Indoor Unit Outdoor Unit Hz - Volts Voltage Range MCA MFA RLA W FLA W FLA
FTX30NVJU RK30NMVJU
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
17 20 16.25 93 0.62 64 0.37
60 - 230
FTX36NVJU RK36NMVJU
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
17 20 16.25 123 0.83 64 0.37
60 - 230
FTX30NVJU RX30NMVJU
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
19.8 20 18.25 93 0.62 64 0.37
60 - 230
FTX36NVJU RX36NMVJU
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
19.8 20 18.25 123 0.83 64 0.37
60 - 230
Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is the max current that comes in cooling operation and heating
operation.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of a fuse, use a circuit breaker.
5. Be sure to install a ground leak detector.
(This unit uses an inverter, which means that a ground leak detector
capable of handling high harmonics must be used in order to prevent
malfunctioning of the ground leak detector.)
MFA : Max. fuse amps (A)
RLA : Rated load amps (A)
OFM : Outdoor fan motor
IFM : Indoor fan motor
W : Fan motor rated output (W)
FLA : Full load amps (A)