Specifications

Troubleshooting SiBE04-624_B
92 Service Diagnosis
Troubleshooting
Note: 1. Be careful not to break the electrode in cleaning.
2. Since the electrode part is electrified in high voltage, be sure to pull out the power supply
plug or turn the breaker off while cleaning the electrode part. (Touching in electrifying results
in electrical shock.)
Clean the streamer unit.
Clean the streamer unit.
Install the streamer unit
surely.
Correct the connection.
Replace the limit switch.
Replace the harness.
Replace the streamer unit
PCB.
(R18121)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Dust or drip of water is
on the streamer unit.
YES
NO
NO
YES
Does the multi-colored
indicator lamp blink about 1
minute after air purifying
operation starts?
NO
YES
Is the streamer unit
installed surely.
NO
YES
Turn off the power supply
(Turn off the breaker).
Check the connector connection
(S52).
* Connect the connector again for
ensuring the connection.
Check the harness.
Normal?
NO
YES
Is the limit switch normal?
YES
Broken?
NO