Specifications
SiBE04-624_B Main Functions
Function and Control 43
1.17 MOLD PROOF Operation
This is an integrated naming of functions of inside drying and moisture exhaustion. Drying inside
the air conditioner prevents mold and odors from growing.
Operation Operation can be selected from automatic and manual.
Automatic operation
If MOLD PROOF operation is set ON, the MOLD PROOF operation starts automatically after
“SARARA” DRYING or COOLING operation. Operation starts depending on the amount of
time the unit has been run. (approximately once every 2 weeks)
Manual operation
Features
Time chart
Operation runs about for 3 hours while changing colors of the multi-colored indicator lamp.
MOLD PROOF operation
(Hold down for 2 seconds.)
(R13892)
Indoor fan
Horizontal flap
Compressor
Damper
Moisture discharge fan
Start
Complete
Cooling Stop
3 hours
(R13893)
ON
OFF
Fully opened
Exhaust side
Heating Min.
OFF
Minimum open
Fully closed
LLL tap
OFF
Pre-drying
10 min.
Drying by
heating 30 min.
Finish up drying
operation 80 min.
Thorough operation
60 min.
Discharge
moisture
Discharge moisture
while heating and
drying the heat
exchanger
Perfectly dry the inside by
short circuit blowing +
discharge
Lower relative humidity and
inactivate fungi by short circuit
heating + discharge