Specifications

SiBE04-624_B Control Specification
Function and Control 57
2.2.4 3-minute Standby
Turning on the compressor is prohibited for 3 minutes after turning it off.
(Except when defrosting.)
2.2.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not activated when defrosting.)
: The upper limit of frequencies G and H are the same.
Cooling Heating
A (Hz) 52 48
B (Hz) 54 58
C (Hz) 78 80
D (Hz) 98 98
E (seconds) 220 220
F (seconds) 140 140
G (seconds) 60 60
H (seconds) 60 60
(sec.)
Time
(R13906)
(Hz)
Frequency
C
D
B
EFG
H
A