Installation Manual Daikin McQuay ThinLine™ Horizontal Fan Coils and Cabinet Unit Heaters IM 1152 Group: Fan Coil Part Number: 910139947 Date: December 2012 Type FC and FH Horizontal Design Exposed Horizontal Cabinet Fan Coil Recessed Horizontal Cabinet Fan Coil Concealed Horizontal Fan Coil Concealed Horizontal Unit Heater © 2012 McQuay International
Table of Contents Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Controls and Thermostats. . . . . . . . . . . . . . . . . . . . . 20 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3-Position Fan Switch with Manual On-Off Receiving and Storage . . . . . . . . . . . . . . . . .
Introduction Daikin McQuay Thinline™ Horizontal Fan Coils are intended for use in single zone applications. They are available in sizes from 200 to 1200 cfm. Figure 2 describes the main features of these units and can be referred to for component placement. These units are available in two-pipe configurations with one hydronic coil, with or without electric heat. They are also available in four-pipe configurations with a primary coil and a secondary reheat or preheat coil.
Introduction Safety CAUTION Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations. Have a fire extinguisher available. Follow all warnings and cautions in these instructions and attached to the unit. Consult applicable local building codes and National Electrical Codes (NEC) for special requirements. Recognize safety information. When you see a safety symbol on the unit or in these instructions, be alert to the potential for personal injury.
Introduction IMPORTANT This product was carefully packed and thoroughly inspected before leaving the factory. Responsibility for its safe delivery was assumed by the carrier upon acceptance of the shipment. Claims for loss or damage sustained in transit must therefore be made upon the carrier as follows: VISIBLE LOSS OR DAMAGE Any external evidence of loss or damage must be noted on the freight bill or carrier’s receipt, and signed by the carrier’s agent.
Installation Uncrating and Inspecting the Unit 1. Carefully remove the packaging, remaining alert to any signs of shipping damage. Be careful not to discard components that may be included with the packaging. 2. If the unit is damaged, file a claim with the carrier. Notify the local Daikin McQuay representative immediately. 3. You may want to retain some or all of the packaging to provide jobsite unit location information and temporary protection for the fan coil after installation.
Installation Recommended Maintenance Clearance Cabinet units have removable bottom and side panels for easy access to components for service and maintenance. The fan assembly and main drain pan are easily removable from the bottom for cleaning. See Accessing/Removing the Main Fan Deck and Motor Assembly on page 18 for more information. Figure 5 shows recommended maintenance clearances for hideaway units.
Installation Piping Connection Recommendations General Guidelines • Piping can be steel, copper or PVC, but must comply with local codes. IMPORTANT Venting is required on the return piping for secondary preheat or reheat coils. It is included on factory-built piping packages, but must be added by the installing contractor for field-installed piping.
Installation Drain Piping • Condensate piping can be steel, copper, or PVC. A means of disconnection must be furnished to facilitate fan deck removal. • No point of the drain system may be above the drain pan of any unit. • Pipe insulation is recommended to avoid condensation. • Suggested slope of the drain pipe is at least 1/8" per foot to facilitate adequate condensate drainage but local code requirement should prevail.
Installation If the unit does not have a factory-installed valve & piping package, the changeover switch or sensor can be ordered for field installation. The installer should attach the sensor or auto changeover switch parallel to and in direct contact with the supply water pipe. NOTE: The installer is responsible to ensure the changeover sensor is installed in a location that can sense active water temperature.
Installation Two-pipe systems with electric heat Standard Electrical Connection The electric heating coil is designed to be the total source of heat for the unit. If used for auxiliary intermediate season heating, additional control is required. A second changeover switch is required. For units ordered with intermediate electric heat, the second changeover switch is factory installed.
Installation Electrical Data ECM Blower The wiring diagram for the unit is attached to the exterior of the blower housing. See Figure 10. Be sure the available power is the same voltage and phase as that shown on the unit data plate. See Figure 3, for the location of the data plate. See page 40 through page 42 for typical wiring diagrams. If the unit is equipped with an ECM blower, additional steps may be required during the air balancing process. The ECM blower is controlled by a control board.
Accessories Condensate Overflow Detection Device Electric Heat Over-Temp Reset Button The condensate overflow detection device is a factoryinstalled option on fan coils. This device has a condensate overflow floater with dry contacts and is connected to the LV interface or MicroTech board. See Figure 12. The electric heat options comes with two over-temperature switches. The first resets automatically when the overtemperature condition no longer exists.
Initial Start Up Cleaning & Flushing the Water System • Prior to first operation of any unit, clean and flush the water circulating system of all construction dirt and debris. • If units are equipped with water shutoff valves, either electric or pressure operated, connect the supply and return runouts together at each unit location. This will prevent the introduction of dirt into the unit. See Figure 15.
Initial Start Up Equipment Start Up Check List IMPORTANT Fan coils must be filled with water before operating a circulating pump. Filling the system properly will result in immediate lubrication of the bearings. The pump bearings should not be allowed to operate dry.
Initial Start Up General Maintenance Normal maintenance on all units is generally limited to filter changes and cleaning the condensate drain pans. Units are provided with permanently lubricated motors and require no oiling even though oil caps may be provided. Figure 16: Filter Removal for Units with Bottom Returns Record performance measurements of volts, amps, and water temperature differences (both heating and cooling).
Initial Start Up Electric Resistance Heater Assembly Condensate Drain Pans Electric resistance heaters typically require no periodic maintenance when the unit’s air filters are changed properly. Other conditions and equipment in the system may affect the operation and service life of the heaters. The most important operating conditions for an electric heater is airflow and supply voltage. As a rule, Daikin McQuay recommends operating the electric heater on the High speed, never on Low.
Maintenance Blower Dirt and dust should not be allowed to accumulate on the blower wheels or housing (see typical, Figure 21). Excessive debris can result in an unbalanced blower wheel condition which can damage the wheel and/or motor. The wheel and housing should be cleaned periodically using a brush and vacuum cleaner. Care must be taken to not dislodge the factory balancing weights on the blower blades.
Maintenance Replacement Parts Factory replacement parts should be used wherever possible to maintain the unit’s performance, service life, operating characteristics and testing agency listings. Replacement parts may be purchased through a local Daikin McQuay sales representative. Contact your local Daikin McQuay sales representative or Daikin McQuay Parts before attempting any unit modifications.
Controls and Thermostats Controls Low-Voltage (LV) Interface Board A wide variety of control options are available for Daikin McQuay ThinLine Horizontal Fan Coils, both unit-mounted and remote-mounted. This section provides a brief overview of these options and their operation. For more complete information, contact your Daikin McQuay representative. The low-voltage interface board is used with any remote (wall mounted) Daikin McQuay thermostat or control.
Controls and Thermostats MT155 Thermostat For more details refer to page 50. The MT155 series thermostat provides on-off control for low-voltage or linevoltage valves and fan motors. This thermostat is designed as a remote-mount with connection to the LV interface board mounted on the fan coil unit. Options include manual or automatic changeover and three-speed fan control for continuous or cycling fan operation.
Controls and Thermostats Digital Thermostats Daikin McQuay offers a broad range of remote, wall-mounted digital thermostats with the capability to control OnOff, 3-wire and proportional modulating valves and Normally-Closed or NormallyOpen actuator valves. For more information, refer to Daikin McQuay publications ED 18513 and ED 18527.
Controls and Thermostats T180 Programmable Thermostat MicroTech III Controller Daikin McQuay offers two different 7-Day Programmable Digital Heating/Cooling Thermostat with constant fan or Fan cycled, On/Off Valve Control depending on the fan speed control. The thermostat interface contains buttons for use in navigation to accompanying menus/screens and for performing specific operations. Detailed installation instructions and modes of operation can be found in Addendum IM 1152 — MT180 on page 54.
Controls and Thermostats Sensors Room Temperature Sensor with Setpoint Adjustable Module and Fan Speed Control The Digitally Adjustable sensor provides the ultimate of temperature control and display, simple user interface, alarm annunciation, and alarm reset. The easy to ready LCD clearly identifies the system operating mode including occupied/ unoccupied mode, fan operation and control, unit status, timed override status, alarm annunciation, and energy savings mode through a series of recognizable icons.
Controls and Thermostats 8. Connect stripped, labeled wires to matching terminals on the temperature sensor. Refer to Figure 29 for wiring details. 9. Tighten screws on terminal connections. Gently tug wire to check for secure connections. Confirm that each wire is connected to the proper terminal. 10. Seal the hole where the wire enters through the wall behind the temperature sensor, with non-flammable insulation or putty. 11. Replace cover on wall temperature sensor by snapping it in place. 12.
Physical Data Unit Data Table 1: Physical Data: Coils, Fans, Motors and Filters Size 02 Size 03 Size 04 Size 06 Size 08 Size 10 Size 12 1.08 (1004) 1.08 (1004) 1.43(1323) 2.11(1962) 2.46(2281) 3.14(2917) 3.83(3559) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) Primary Coil Data Face Area, ft2 (cm2) Fins/inch (cm) Connection Size 1/2" Nominal Copper (5/8" OD) Coil Dimensions 2-Row L × D × H, in (cm) 17.3 × 1.7 × 9 (43.9 × 4.4 × 22.9) 17.3 × 1.7 × 9 (43.9 × 4.4 × 22.
Physical Data Unit Dimensions Figure 31: Dimensions – Hideaway Fan Coil, Front Discharge – Free Return Reheat coil shown Top View 5.01 (4) Mounting Holes ⅜" × ⅝" Control Box ⅝" O.D. Coil Connections (Typical) 1.0 1.73 C 6.0 ○ × REFERENCE POINT F D 0.5 H 1.54 0.64 2.49 1.25 4.35 3.4 B 15.28 (2) L 0.68 1.62 REFERENCE POINT REFERENCE POINT ○ × ○ × 9.25 6.75 9.47 K 9.42 9.86 8.08 5.21 1.5 A 0.5" O.D. Overflow Connection 3.11 Front View Dimension 0.75" O.D.
Physical Data Figure 32: Dimensions – Hideaway Fan Coil With Plenum, Front Discharge – Rear Return Top View G 5.01 (4) Mounting Holes Secondary Drain Pan (1) ⅜" × ⅝" Control Box ⅝" O.D. Coil Connections (Typical) NOTES: 1.0 C (1) Secondary drain pan is only supplied with factory-provided piping packages (2) For units without mixing box 6.0 ○ × REFERENCE POINT F D 0.5 H 0.64 21.5 (2) 2.49 20.2 (2) 4.35 5.4 B 17.3 (2) 0.68 1.62 REFERENCE POINT REFERENCE POINT ○ × ○ × 9.25 8.8 6.
Physical Data Figure 33: Dimensions – Hideaway Fan Coil With Plenum, Front Discharge – Bottom Return Top View G 5.01 0.952 0.952 E (4) Mounting Holes ⅜" × ⅝" Return Air Opening Control Box ⅝" O.D. Coil Connections (Typical) NOTES: 1.0 C (1) Secondary drain pan is only supplied with piping packages 6.0 ○ × REFERENCE POINT F D 0.5 H 0.64 2.49 4.35 3.4 20.2 B 17.3 0.68 1.62 REFERENCE POINT REFERENCE POINT ○ × ○ × 9.25 6.75 8.08 9.47 11.13 9.42 9.86 0.647 5.21 0.75" O.D.
Physical Data Figure 34: Dimensions – Cabinet Fan Coil, Front Discharge – Rear Return Control Box Top View 35.0 28.0 (4) ¾" Mounting Holes REFERENCE POINT ○ × C.XX 2.375 D 4.5 NOTE: A 15.28 (1) Unit is shown with duct collar flanges for return and discharge openings Coil connections are 5/8" O.D. F 15.28 S E S REFERENCE POINT ○ × Front View 2.23 3.98 5.48 6.48 8.91 11.75 14.0 12.00 3.51 1.0 5.81 1.0 Back View REFERENCE POINT ○ × Side View 7.26 9.01 8.82 7.55 10.
Physical Data Figure 35: Dimensions – Cabinet Fan Coil, Front Discharge – Bottom Return Return t Control Box Top View 35.0 28.0 (4) ¾" Mounting Holes REFERENCE POINT ○ × C.XX 2.375 D 4.5 NOTE: Coil connections are 5/8" O.D. A 15.28 (1) Unit is shown with duct collar flange for discharge opening F 15.28 REFERENCE POINT ○ × 2.23 3.98 5.48 6.48 8.91 11.75 12.00 14.0 15.14 3.51 Bottom View 5.81 Back View 15.2 S S 12.04 (4) 2" Drain Knockouts 8.82 E 10.
Physical Data Figure 36: Dimensions – Cabinet Fan Coil, Bottom Discharge – Rear Return Control B Box Top View 35.0 28.0 (4) ¾" Mounting Holes REFERENCE POINT ○ × C.XX 2.375 D 4.5 Coil connections are 5/8" O.D. A 15.28 F 15.28 REFERENCE POINT Discharge Bottom View S 2.73 E S ○ × 2.23 7.5 3.98 5.48 6.48 Return 8.91 11.75 12.00 14.0 15.14 3.51 5.81 Back View 7.26 9.01 15.2 10.09 (4) 1" Electrical Power Knockouts (8) 2" Piping Knockouts 12.
Physical Data Figure 37: Dimensions – Cabinet Fan Coil, Bottom Discharge – Bottom Return Return t Top View Box 35.0 28.0 (4) ¾" Mounting Holes REFERENCE POINT ○ × C.XX 2.375 D 4.5 Coil connections are 5/8" O.D. A 15.28 F 15.28 REFERENCE POINT ○ × 2.73 2.23 3.98 5.48 6.48 7.5 Discharge 8.91 11.75 12.00 14.0 15.14 3.51 Bottom View 5.81 Back View 15.2 8.82 S E S 10.09 (4) 1" Electrical Power Knockouts (8) 2" Piping Knockouts Return 7.26 9.01 12.04 (4) 2" Drain Knockouts 2.
Physical Data Figure 38: Dimensions – Recessed Cabinet Fan Coil with Ceiling Plate 30.34 39.34 NOTES: (1) See sheet #1 for unit dimensions (2) For installations with height restrictions below 14", use the fixed trim flange accessory 4.5 2.0 typ. 7.0 7.0 X 2.0 typ. Y Bottom View Unit Cabinet 14.5" min. 16.0" max. Detail A Plate to cabinet connection for fully recessed units 3.0 Detail A Floating Ceiling Panel Side View Figure 39: Dimensions – Trim Flange Mount 39.
Valve and Piping Packages Factory-Installed Valve and Piping Packages Factory valve and piping packages are available for both two-pipe and four-pipe systems with either right or left hand connections. Four-pipe systems can be configured with the heating and cooling connections on the same or opposite sides of the unit. Packages can be either factory-installed or factory-assembled and shipped loose with the unit. All factory-assembled packages are fully leak tested.
Valve and Piping Packages Enhanced Packages Deluxe Packages Enhanced valve and piping packages add a strainer to the Basic package supply water pipe. The strainer is attached to the supply water pipe at the coil connections. The strainer body is cast brass construction with a stainless steel mesh that is easy to remove for cleaning. Deluxe valve and piping packages add a strainer to the Premium package. The strainer is available with or without an optional draining (blow-off) valve.
Valve and Piping Packages Control Valve Options Except for Shut-off Only packages, all valve and piping packages include control valves for controlling water flow. All Daikin McQuay control valves are factory assembled and mounted in the supply water pipe downstream of the coil.
Valve and Piping Packages Figure 47: Factory-installed Valve & Piping Packages (right-hand shown) Connecting 2-PipeCooling CoolingOnly, or Heating Connecting Pipe Pipe Locations: Locations: 2-Pipe Right-hand Deluxe Package shown Deluxe Package shown, see schematic (page 2) for the list of components selected for this package 5.38 3.42 REFERENCE POINT ○ × Primary Supply Front View Primary Return 0.50‡ 1.5† 7.0 20.25 B A † Overflow Connection ‡ Drain Connection REFERENCE POINT ○ × 4.
Valve and Piping Packages Connecting PipePipe Locations: 4-Pipe Cooling and Heating,Same-side, Same-sideRight-hand Connecting Locations: 4-Pipe Cooling & Heating DeluxeDeluxe Package shown shown, see schematic (page 2) for the list of components selected for this package Package 7.7 REFERENCE POINT ○ × 10.35 5.38 3.42 Primary Supply Secondary Return Primary Return Secondary Supply 0.50‡ 1.5† 7.0 Front View † Overflow Connection ‡ Drain Connection 20.
Wiring Diagram Figure 48: Fan Coil Wiring Diagram – Typical Low Voltage Interface Board and ECM 40 IM 1152
Wiring Diagram IM 1152 41
Wiring Diagram Figure 49: Fan Coil Wiring Diagram – Typical with Unit-mounted 3-speed Switch and PSC Motor(s) 42 IM 1152
Wiring Diagram IM 1152 43
Wiring Diagram Figure 50: Fan Coil Wiring Diagram – Typical No Controls and PSC Motor(s) 44 IM 1152
Model Number Description Model Number Description: Fields 1—21 Field Code 1 FC 2 HC 3 1 4 02 5 A 6 A 7 G 8 M 9 Y 10 YY 11 W 12 3 13 12 14 R 15 F 16 T 1. Unit Type 12. Primary Coil Rows • FC = fan coil • FH = cabinet unit heater 2. Product Identifier • 2 = 2 row • 3 = 3 row • 4 = 4 row 13. Primary Coil Fins Per Inch • HC = horizontal, exposed • HH = horizontal, concealed 3. Design Series • 1 = Design 1 4.
Model Number Description Table 3: Model Number Description: Fields 22—41 Field Code 22 YY 23 W1 24 12 25 R 26 F 27 T 28 Y 29 000 30 Y 31 P 32 PSC 33 S 34 3 35 Q 36 Y 22. Not currently used 30. Not currently used • YY = none 23. Reheat Coil Type • YY = none 31. Drain Pan Material • W1 = water standard capacity • W2 = water high capacity • S1 = standard capacity • S2 = high capacity • YY = none 24. Reheat Coil Fins Per Inch • G = galvanized • S = stainless steel 32.
Model Number Description Table 4: Model Number Description: Fields 42—56 Field Code 42 Y 43 Y 44 Y 45 RL 46 MOR 47 Y 48 49 50 3MOU YYYY 3MOU 51 Y 52 Y 42. Network Communication Card 47. Timed Override • Y = none 43. Changeover Type • Y = none 48. Valve - Primary Coil • Y = none • A = auto • M = manual • U = user selectable 44. Programmability • See Table 4 49. Valve - Preheat Coil • Y = none 45.
Model Number Description Table 5: Model Number Description: Fields 57—72 Field Code 57 Y 58 Y 59 Y 60 Y 61 S 62 18 63 P 64 I 65 00 66 S 67 00 68 00 69 30F 57. Filter Status Sensor 68. Right Hand End Pocket Extension • Y = none • X = special 58. Fan Status Sensor • 00 = none • 04 = 4 inch extended length 69. Subbase (not applicable) • Y = none • X = special 59. Future Control Function 70. Discharge Air - Outlet • Y = none 60. Future Control Function • Y = none 61.
Model Number Description Table 6: Model Number Description: Fields 73—78 Field Code 73 74 YYY Y 75 A 76 S 77 Y 78 1 73. Special Options 77. Extended Warranty • YYY = none 74.
Addendum IM 1152 — MT155 Installation and Maintenance Manual IM 1014 MT 155 Thermostat Group: Applied Air Systems Part Number: 910102989 Date: August 2009 Installation Figure 1: Removing Jumper JP-1 INSTALL COVER LOCKING SCREW DANGER READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT. To avoid electrical shock or damage to equipment, disconnect power before installing or servicing.
Addendum IM 1152 — MT155 for fan continuous operation or is dependant upon connection to the fan supply input . When internally wired for fan continuous operation, the fan will be off when the system switch is off. When dependant upon external connections the fan may not be off with the system switch in the off position. The fan supply input is switched to fan speed outputs (HI MED - LO). 7 Observe electrical ratings. Thermostatic outputs are pilot duty only.
Addendum IM 1152 — MT155 Installation and Maintenance Manual Field installation of Thermostat (MTA155 or MTB155) and 24V valve packages on Vertical Thinline 3G fan coil units with factory-installed Low Voltage Interface Board General DANGER READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT. Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.
Addendum IM 1152 — MT155 Figure 2: Low Voltage Interface Board shown with all additional support options Line Voltage Hi-Med-Lo Fan motor control FA Clg. 24vac valve actuators inputs Htg. 24vac valve actuators inputs Room air or return air temperature sensor Wiring Harness Clg. 24vac valve actuators – with quick connects t Pipe sensor or ACO switch Condensate overflow sensor output Remote thermostat 24 VAC power Htg.
Addendum IM 1152 — MT155 Figure 4: Thermostat TB155 autochangeover to be used with On-Off 24V valve packages, SPDT ACO and unit-mounted Low Voltage Interface Board Figure 5: Automatic changeover switch (SPDT ACO Kit P/N 039398600) • 10K Return Air Sensor - PN 107345501 for unit-mounted applications only (for wall-mounted applications the sensor is imbedded with the thermostat) Step 1: Installing valve packages • Solder the appropriate inlet and outlet CW pipe connections from the valve package to the coil
Addendum IM 1152 — MT158 Installation and Maintenance Manual MTA 158 Microprocessor Thermostat On/Off Controller Installation IM 1015 Group: Applied Air Systems Part Number: 910102990 Date: August 2009 LINE V OLTAG E C ONNE C T IONS Figure 1: Wiring Diagram for On/Off Ouput Configuration DANGER READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT.
Addendum IM 1152 — MT158 Thermostat Operation These thermostats are designed to control On-Off, N.O. and N.C. valves, relays and Erie® three wire floating valves. These units may include a fan switch with one or more fan speed selections. Mode Button Operation OFF: All thermostat outputs are off, fan is still operational if connected to manual fan speed switch. AUTO: The thermostat automatically selects heating or cooling mode depending on the set point and room temperature.
Addendum IM 1152 — MT158 Figure 3: Circuit Board Jumpers ON 2 3 4 5 6 J P4 AUTO 15 16 17 5 6 7 J P1 1 2 3 4 10 11 12 13 1 DIP S WIT C H Table 3: Circuit Board Jumper Configuration Jumper Designation Jumper Installed ON Jumper Removed JP1 Local Sensing Remote Sensing JP4 2 Pipe System* 4 Pipe System Application Notes 1 When no pipe sensor is used the main output controls cooling and the secondary output controls heating.
Addendum IM 1152 — MT158 Installation and Maintenance Manual IM 1016-1 MTB 158 Microprocessor Thermostat On/Off and 3-Wire Controller Group: Applied Air Systems Part Number: 910102991 Date: November 2010 CAUTION DANGER Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE. To avoid electrical shock or damage to equipment, disconnect power before installing or servicing.
Addendum IM 1152 — MT158 2 For wall installations, mount the thermostat on an inside wall approximately 5 feet above the floor. The location should provide circulation at average room temperature. Avoid direct sunlight or sources of hot or cold air in the room or wall. 3 Remove the cover. Mount thermostat base assembly to the outlet box using the screws provided, tighten the screws evenly but do not over tighten. Connect wires as shown in the appropriate wiring diagram for your thermostat style.
Addendum IM 1152 — MT158 Application Notes Figure 3: Circuit Board Jumpers ON 2 3 4 5 6 cooling and the secondary output controls heating. J P4 AUTO input for water system operation and in the main duct system for forced air operation. 10 11 12 13 15 16 17 1 2 3 4 2 The pipe sensor should be mounted on the main coil 1 DIP S WIT C H 1 When no pipe sensor is used the main output controls 5 6 7 3 The set point and operating mode will be retained on a J P1 loss of power.
Addendum IM 1152 — MT168 Installation and Maintenance Manual IM 1017 MT 168 0-10 VDC/4-20mA Thermostat Group: Applied Air Systems Part Number: 910102992 Date: August 2009 Installation Figure 1: Mounting DANGER READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT. Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.
Addendum IM 1152 — MT168 5 Connecting a jumper between terminals 16 and 17 will disable the secondary output and change the main output to heat mode. 6 Connection of a 24 VAC set-back signal will force the control into unoccupied mode (see diagram). Pressing an arrow key or the mode buttons on the thermostat cover will disable the setback input for one hour. 7 Remove the LCD plastic protective film to complete the installation. Reinstall the cover assembly. Install cover locking screw provided.
Addendum IM 1152 — MT168 Table 3: Dip Switch Configuration Switch Closed On* Open Off 1 Not Used Not Used 2 Staged Heat 3°F Diff. (Term. 13) Aux. Heat No Diff. (Term. 13) 3 F Display C Display 4 Main & Sec. Outputs 0-10 VOC (Term. 10 & 11) requires JP4 & JP5 Main & Sec. Outputs 4-20 mA (Term. 10 & 11) Remove JP4 & JP5 5 Operating Position Not Used 6 Setback= 90°F & 50°F Setback = 85°F & 60°F Note: * On is with the dip switch handle to the right. See diagram below.
Addendum IM 1152 — MT170 Installation and Maintenance Manual T170 Thermostat IM-846 Group: Fan Coil Part Number: 910102993 Date: July 2006 24 VAC/120–277 VAC 3-Speed Fan Control (Continuous or Cycling) or Staged Fan Control US © 2006 McQuay International 800-432-1342 www.mcquay.
Addendum IM 1152 — MT170 Table of Contents Table of Contents Installation Instructions . . . . . . . . . . . . . . . . . . . . . . 3 Thermostat Model and Part Number . . . . . . . . . . . . . . . . . . . . . . . . 3 Optional Occupancy Detection Sensors/Kits. . . . . . . . . . . . . . . . . . 3 Mounting and Wiring the Thermostat . . . . . . . . . . . . . . . . . . . . . . . 3 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Thermostat Button Operation . . . . . . . . . . . . .
Addendum IM 1152 — MT170 Installation Instructions Installation Instructions Mounting and Wiring the Thermostat WARNING • BEFORE ATTEMPTING TO INSTALL, OPERATE, OR SERVICE THIS THERMOSTAT, CAREFULLY READ THESE INSTRUCTIONS. • Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE. • To avoid potential fire and/or explosion, do not use in potentially flammable or explosive atmospheres.
Addendum IM 1152 — MT170 Installation Instructions 5 On the circuit board, set the voltage selection switch Figure 3: Wiring diagram (Figure 2) to the appropriate voltage for the application Setback input/door switch White/Black Note: The circuit board is shipped with the voltage selection switch in the 110-227 V position. For 24 VAC use, the switch must be in the 24 V position. Before applying power, the voltage selection switch must be in the appropriate position.
Addendum IM 1152 — MT170 Operation Operation Thermostat Button Operation UP/Down Arrow Button Operation The thermostat interface (Figure 4) contains buttons for use in navigating to accompanying menus/screens and for performing specific operations. These buttons and operations are described below. Use the Up and Down arrow buttons (Figure 4) to increase or decrease the temperature.
Addendum IM 1152 — MT170 Operation Thermostat Menu Functions The thermostat menu contains nine functions which can be accessed using controls on the thermostat. Accessing the menu functions and details of each function are described below. 5 Range limit high When this function is selected, the current maximum temperature range adjustment, SET POINT icon, and LO icon appear. To increase or decrease the value, press the up or down arrow button.
Addendum IM 1152 — MT170 Operation Fan Operation The thermostat may be factory configured for standard or staged fan operation. Standard Fan Configuration (TA170-001) Units with standard fan operation (Figure 8) have a selectable fan Speed button. Figure 8: Standard fan operation Fan ON: fan is on continuously. Fan AUTO: fan cycles on with demand. S PE ED: Fan s peed is selected by the user .
Addendum IM 1152 — MT170 Operation Fancoil Operation Fancoil operation is either a 2-pipe or 4-pipe configuration which is determined by jumper selection JP4 (see “Mounting and Wiring the Thermostat” on page 3). 2-Pipe Operation In this configuration, the thermostat permanently disables the secondary output and disables the fan from cycling in an invalid mode. The main output configuration is dependent on the pipe sensor input.
Addendum IM 1152 — MT170 Optional Occupancy Detection Equipment Operation Optional Occupancy Detection Equipment Operation The T170 thermostat can be used with optional S200 series occupancy detection equipment. Purchasing and installing this equipment to compliment the thermostat adds energy savings by setting back HVAC operation during occupied and unoccupied times. Optional detection equipment configurations and operation are described below.
Addendum IM 1152 — MT170 Optional Occupancy Detection Equipment Operation SD200-001 Occupancy Sensor Operation The SD200-001 occupancy sensor (Figure 11) serves as a master sensor for a guest room HVAC management system. The sensor provides HVAC operation according to occupancy status, as well as door/window switch monitoring, selectable high/low temperature setback, form-C output, slave sensor connectivity, and a five minute door open HVAC shut-off.
Addendum IM 1152 — MT170 Optional Occupancy Detection Equipment Operation SD200-002 Occupancy Sensor Operation The SD200-002 occupancy sensor serves as a stand alone master sensor for a guest room HVAC management system. The sensor provides HVAC operation according to occupancy status, as well as selectable high/low temperature setback, form-C output, and a five minute door open HVAC shut-off. This system provides basic room setback and is ideal for control of HVAC in commercial spaces.
Addendum IM 1152 — MT180 Installation and Maintenance Manual IM 1019 Group: Fan Coil Part Number: IM 1019 Date: October 2011 MT 180 Programmable Thermostat © 2011 McQuay International
Addendum IM 1152 — MT180 Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . 3 Applications and features . . . . . . . . . . . . . . . . . . . . . 3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Thermostat Model and Part Number . . . . . . . . . . . . . 4 Optional Sensors/Kits . . . . . . . . . . . . . . . . . . . . . . . . 4 Installing, Mounting and Wiring the Thermostat . . . . 4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Addendum IM 1152 — MT180 Installation Instructions Installation Instructions Specifications WARNING • READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT. • Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
Addendum IM 1152 — MT180 Installation Instructions Thermostat Model and Part Number McQuay offers two different 7-Day Programmable Digital Heating/Cooling Thermostat with constant fan or Fan cycled, On/Off Valve Control depending on the fan speed control used (See Table 2). . Table 2: Thermostat Model and Part Number Model Number Part Number Fan Speed Control TA180-001 TB180-001 910119110 910119111 3-speed fan control Staged fan control • Use copper wire only. Insulate or wire nut all unused leads.
Addendum IM 1152 — MT180 Installation Instructions 5 On the circuit board, set the voltage selection switch Figure 4: Wiring Diagram (Figure 3) to the appropriate position prior to application of power. • 24V = 24 VAC • 110-277 V = 120, 240 or 277 VAC Note: The circuit board is shipped with the voltage selection switch in the 110-227 V position. For 24 VAC use, the switch must be in the 24 V position 6 The circuit board is also equipped with configuration jumpers (JP1, JP3, and JP4 in Figure 3).
Addendum IM 1152 — MT180 Operation Operation Front Panel Reference The thermostat interface (Figure 5) contains buttons for use in navigating to accompanying menus/screens and for performing specific operations. These buttons and operations are described below.
Addendum IM 1152 — MT180 Operation Saving Changes 6 Fan Operation Indicators Table 10: Fan Operation Indicators Overview Menu FAN ON AUTO HI M LO Description “FAN” will be always be lit in conjunction with “ON” or “AUTO” Indicates constant, continuous fan operation Indicates fan is only on with heating or cooling demand Indicates high speed fan; always lit in conjunction with “ON” or “AUTO” Indicates medium speed fan; always lit in conjunction with “ON” or “AUTO” Indicates low speed fan; always lit in co
Addendum IM 1152 — MT180 Operation System Button Operation Fan Button Operation Pressing SYSTEM will light up the five system mode options described below. Press SYSTEM to scroll through the options. As you scroll, the current option will be blinking. To select the blinking option, wait for the five-second timeout, which saves your option and returns you to the thermostat’s default display. Pressing FAN will light up the six fan mode options described below. Press FAN to scroll through the options.
Addendum IM 1152 — MT180 Operation Setting the Clock & Day 1 Press PROGRAM once. 2 Press Ÿor źto scroll until “CLOCK” is blinking. To select, press PROGRAM once. 3 Press Ÿor źto scroll through “24Hr”, “AM”, “PM” options. “24Hr” sets your thermostat to a 24-hour clock. “AM” and “PM” sets your thermostat to a 12-hour clock. To select your preference, press PROGRAM once. 4 Press Ÿor źto scroll to the current hour. To select, press PROGRAM once. 5 Press Ÿor źto scroll to the current minute.
Addendum IM 1152 — MT180 Operation Copy Feature 1 Press PROGRAM once. 2 Press Ÿor źto scroll until “COPY” is blinking. To select, press PROGRAM once. 3 Press Ÿ or źto scroll to the individual day you want to copy from. “DFLT” (the default Factory Program) is also a copy option. To select your preference, press PROGRAM once. 4 Press Ÿ or źto scroll to the day or group of days you want to copy to. To select, press PROGRAM once.
Addendum IM 1152 — MT180 Operation System Check-out To verify thermostat operation after mounting and wiring it, perform the following: Figure 8: Local sensor installation 1 Energize the system. 2 Set fan to ON. Select each fan speed (TA180 Models) to verify operation. 3 Set the System button to AUTO, or available selection. 4 Using the UP arrow, adjust temperature more than 5°F above the room temperature to cycle on heating.
Addendum IM 1152 — MT180 Technical and Application Notes Technical and Application Notes Fan Operation Fancoil Operation The thermostat may be factory configured for standard or staged fan operation. Fancoil operation is either a 2-pipe or 4-pipe configuration which is determined by jumper selection JP4 (see Installing, Mounting and Wiring the Thermostat‚ page 4).
Addendum IM 1152 — MT180 Technical and Application Notes Time-Based Purge (Default) 1 The time-based purge cycle will start a 3-min purge cycle and enable the Main Output if any of the following conditions occur: transition from OFF to AUTO mode, Reset event, power cycle, and/or 1-hour timer expires.
Addendum IM 1152 — MT180 Optional Occupancy Detection Equipment Operation Optional Occupancy Detection Equipment Operation The T180 thermostat can be used with optional S200 series occupancy detection equipment. Purchasing and installing this equipment to compliment the thermostat adds energy savings by setting back HVAC operation during occupied and unoccupied times. The sensor switch is open in occupied mode and closed in unoccupied mode.
Addendum IM 1152 — MT180 Optional Occupancy Detection Equipment Operation SD200-001 Occupancy Sensor SD200-002 Occupancy Sensor The SD200-001 occupancy sensor (Figure 12) serves as a master sensor for a guest room HVAC management system. The sensor provides HVAC operation according to occupancy status, as well as door/window switch monitoring, selectable high/low temperature setback, form-C output, slave sensor connectivity, and a five minute door open HVAC shut-off.
Addendum IM 1152 — MT180 Annex I Annex I Table 18: Custom Program Worksheet Day Time Period Start Time Heat Setpoint Temperature Cool Setpoint Temperature Wake Day Monday Evening Sleep Wake Day Tuesday Evening Sleep Wake Day Wednesday Evening Sleep Wake Day Thursday Evening Sleep Wake Day Friday Evening Sleep Wake Day Saturday Evening Sleep Wake Day Sunday Evening Sleep 16 McQuay IM 1019
Addendum IM 1152 — MT180 Annex II Annex II Table 19: Service Menu Table Menu Feature 1 F° or C° 3 Fan Off Delay 4 Range Low 5 Range High Range Description / Comments 0- Celsius 1- Fahrenheit (Default) Determines temperature displays in Fahrenheit or Celsius 0-99 Seconds (0- Default) The amount of time (in seconds) the lowest available fan speed will run after the thermostat outputs are disabled.
Addendum IM 1152 — Digitally Adjustable Display Sensor Installation & Maintenance Data IM 1171-2 Group: WSHP/FCU Part Number: 910139264 Date: November 2012 Digitally Adjustable Display Sensor Used With: :DWHU 6RXUFH +HDW 3XPSV :6+3 6HQVRU 3DUW 1R SmartSource™ Units - Models GS & GT Enfinity 8QLWV ZLWK 0LFUR7HFK® III Controls - Models CCH, CCW; VFC, VFW; LVC, LVW; MHC, MHW & VHC, VHF )DQ &RLO 8QLWV )&8 6HQVRU 3DUW 1R Models With MicroTech III Controls 0F4XD\ ,QWHUQDW
Addendum IM 1152 — Digitally Adjustable Display Sensor Contents Overview...............................................................................2 Applications .........................................................................3 Sensor Functions ................................................................3 )DQ &RLO 8QLW 0RGHO :DWHU 6RXUFH +HDW 3XPS 0RGHO Sensor Dimensions ......................................
Addendum IM 1152 — Digitally Adjustable Display Sensor Digitally Adjustable Sensor Applications The display sensor can be used on the products shown in Table 1.
Addendum IM 1152 — Digitally Adjustable Display Sensor Sensor Dimensions Figure 2: Sensor dimensions AC power wiring is present in the same conduit as the signal OLQHV ,I \RX DUH H[SHULHQFLQJ DQ\ RI WKHVH GLI¿FXOWLHV SOHDVH FRQWDFW \RXU 'DLNLQ 0F4XD\ UHSUHVHQWDWLYH Figure 3: Daikin McQuay sensor circuit board Termination 'DLNLQ 0F4XD\ UHFRPPHQGV XVLQJ D WZLVWHG VKLHOGHG SDLU RI at least 22AWG for the power wire connections.
Addendum IM 1152 — Digitally Adjustable Display Sensor Mounting Location Avoid mounting on outside walls or in direct sunlight. Junction Box, (J-Box) 1. Pull the wire through the wall and out of the junction box, leaving about six inches free. 2. Pull the wire through the hole in the base plate. 6HFXUH WKH EDFN SODWH WR WKH ER[ XVLQJ WKH î inch mounting screws provided.
Addendum IM 1152 — Digitally Adjustable Display Sensor Setpoint Analog Range Tolerance Table 3: Setpoint analog range tolerance Adjusting The Setpoint (Temperature or Humidity) Setpoint Analog Tolerance 55° to 95°F Scale -5° to +5°F Scale Terminal 3 Analog Output # °) PLQ # °) PLQ WR YGF # °F # °F WR YGF # °F @0°F WR YGF # °F # °F WR YGF # °) PD[ # °) PD[ WR YGF Sensor Error Sensor Error )XOO 6FDOH § YGF Initial St
Addendum IM 1152 — Digitally Adjustable Display Sensor Display Descriptions Fan Status & Speed Indicators: The Fan Shape, 4 Wavy Lines and “Auto” word indicate Fan and Speed status. “Fan & No Wavy Lines” indicate the fan is Off.
Addendum IM 1152 — Digitally Adjustable Display Sensor System Mode Indication (FCU Only) “Heat/Cool/Auto/Off” The “Heat/Cool/Auto/Off” Mode Indicators on the bottom of the display show the mode status of the sensor and are changed by pushing the System Mode button. “Cool” on the display means the unit will only provide cooling. “Heat” on the display means the unit will only provide heating. “Auto” on the display means the unit switches automatically to provide cooling or heating.
Addendum IM 1152 — Digitally Adjustable Display Sensor Front Panel Button Operation the new occupancy condition remains; otherwise the “U” terminal will return to the original state and the “Occupied” Icon ZLOO ÀDVK WKH GHVLUHG RFFXSDQF\ VWDWH HYHU\ VHFRQGV Up & Down Setpoint Buttons (Temp Or Humidity): 3UHVV WKH 6HWSRLQW ³8S 'RZQ´ %XWWRQV RQFH WR HQWHU WKH 6HWSRLQW $GMXVWPHQW 0RGH 9LHZ WKH GLVSOD\ WR VHH ZKHWKHU the unit is in Temperature or Humidity Setpoint mode.
Addendum IM 1152 — Digitally Adjustable Display Sensor Optional Technician Adjustments P2 P3 P4 Temperature Offset (Factory set to zero). ³83´ WR LQFUHDVH RIIVHW XS WR ³'2:1´ WR GHFUHDVH RIIVHW GRZQ WR Humidity Offset (Factory set to zero).
Addendum IM 1152 — Digitally Adjustable Display Sensor Optional Technician Adjustments 7HPSHUDWXUH 9DOXH +XPLGLW\ 9DOXH Humidity Setpoint. +XPLGLW\ 9DOXH 7HPSHUDWXUH 6HWSRLQW Humidity Setpoint.
Addendum IM 1152 — Digitally Adjustable Display Sensor Diagnostics Problem & Possible Solution (Continued) FAN key does not change Fan Mode &KHFN WR YHULI\ )$1 LV QRW ORFNHG RXW LQ 3URJUDPPLQJ 0RGH 0HQX 3DJH 3 MODE key does not change System Mode &KHFN WR YHULI\ 0RGH LV QRW ORFNHG RXW LQ 3URJUDPPLQJ Mode Menu Page P7. Up or Down key does not change Setpoints &KHFN WR YHULI\ 6HW SRLQWV DUH QRW ORFNHG RXW LQ Programming Mode Menu Page P11.
Addendum IM 1152 — Thermostat Conversion Kit Installation and Maintenance IM 831 Group: Fan Coil Part No: 667757200 Date: May 2006 McQuay® Fan Coil Unit Thermostat Conversion Kit – to Eliminate 3-speed Switch Capability Kit Part No. 107345245 Safety Information The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes. It is the responsibility of the installer to determine and follow the applicable codes.
Addendum IM 1152 — Thermostat Conversion Kit 4. Adjust the dip switch and jumpers to your desired configuration (see thermostat installation manual). 6. 5. Pull off the fan slide switch cap (Figure 3). Figure 4. Thermostat cover without 3-speed switch opening Place the new thermostat cover that does not have the 3-speed switch opening on the thermostat (Figure 4). Note: Be careful not to change the position of the switch you set in Step 2. Figure 3.
Addendum IM 1152 — Automatic Changeover Switch Installation & Maintenance Data IM 763 Group: Fan-coil Part Number: 106333101 Automatic Changeover Switch For Automatic Seasonal Changeover on Two-pipe Systems Date: August 2002 Installation and maintenance are to be performed only by qualified personnel who are familiar with and in compliance with state, local and national codes and regulations, and experienced with this type of equipment.
Daikin McQuay Training and Development Now that you have made an investment in modern, efficient Daikin McQuay equipment, its care should be a high priority. For training information on all Daikin McQuay HVAC products, please visit us at www.DaikinMcQuay.com and click on training, or call 540-248-9646 and ask for the Training Department. Warranty All Daikin McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty.