Service manual

Outdoor Unit SiE18-201
280 Removal Procedure
2. Dismounting the fan
motors
In disconnecting the
connectors, do not pull the
leads, but hold the
connectors and press the
hooks.
1
Disconnect the two fan
motor relay connectors
from the PCB in the
electrical box.
2
The fan motor leads
are hooked in some
locations: one hook for
the upper fan and two
for the lower fan.
3
Undo the lead tie-
wraps first and then the
lead clamp off the
partition board.
4
Disconnect the earth
wire from the upper-
motor mount.
5
Undo the clamp. Precaution in mounting the
motors:
Be sure to secure the motor
leads with the clamps.
Otherwise the leads may get
caught by the fans.
In setting up the fan, put the
partition board piece
between the tie-wraps A and
B and secure the lead.
6
Remove the four
screws from the fan
motor. Then dismount
the fan motor.
Step Procedure Points
Clamp
Clamp
(M1180)
Fan motor lead
(upper fan)
Fan motor lead
Earth wire
Clamp
Fan motor
(M1181)
Lead
Propeller fan
(M1182)