Engineering

EDUS181520C Specifications
Multi-Split Type Air Conditioners RMXS-L Series 15
2
3.2 Combination Capacity
The following capacity tables are for wall mounted type and duct connected type models as representative.
Class 070912151824
Rated Capacity (kBtu/h) 7 9 12 15 18 24
Cooling / heating capacity on the following tables × Rated capacity of each indoor unit
Capacity of each indoor unit =
Total rated capacity of indoor units
For Example: (cooling)
CTXS07J + CTXS12H + FTXS18L + FTXS24L
7 + 12 + 18 + 24 = 61 < 62
52
× 7
Total rated capacity of indoor
units
Cooling capacity of CTXS07J =
Cooling capacity of CTXS12H =
=
=
=
=
61
52
× 12
= 5.967
= 10.229
61
52 × 18
Cooling capacity of FTXS18L =
61
52 × 24
= 15.344
= 20.459Cooling capacity of FTXS24L =
61
=