EDUS04-906_b - Heat Pump H-Series
EDUS04-906_b Split-System Room Air Conditioners H-Series Quaternity 1. 2. 3. 4. 5. 6. 7. Heat Pump FTXG09HVJU FTXG12HVJU FTXG15HVJU RXG09HVJU RXG12HVJU RXG15HVJU Power Supply ..............................................................................................2 Functions.....................................................................................................3 Specifications ..............................................................................................4 Dimensions .
Power Supply EDUS04-906_b 1.
EDUS04-906_b Functions Basic Function Functions Inverter (with Inverter Power Control) Operation Limit for Cooling (°FDB) Operation Limit for Heating (°FWB) Compressor Comfortable Airflow Comfort Control Operation PAM Control Energy Saving During Operation Standby Oval Scroll Compressor Swing Compressor Rotary Compressor Reluctance DC Motor Power-Airflow Flap Power-Airflow Dual Flaps Wide-Angle Louvers Vertical Auto-Swing (Up and Down) Horizontal Auto-Swing (Right and Left) 3-D Airflow Comfort Airf
Specifications 60Hz 230V EDUS04-906_b 3. Specifications 60Hz 230V Indoor Units Models Capacity Rated (Min.~Max.) Moisture Removal Running Current (Rated) Power Consumption Rated (Min.~Max.) Power Factor EER (Rated) COP (Rated) Energy SEER/HSPF Efficiency Liquid Piping Gas Connections Drain Heat Insulation Max. Interunit Piping Length Max.
EDUS04-906_b Specifications 60Hz 230V 60Hz 230V Indoor Units Model FTXG15HVJU RXG15HVJU Outdoor Units Capacity Rated (Min.~Max.) Moisture Removal Running Current (Rated) Power Consumption Rated (Min.~Max.) Power Factor EER (Rated) COP (Rated) Energy SEER/HSPF Efficiency Liquid Piping Connections Gas Drain Heat Insulation Max. Interunit Piping Length Max.
Dimensions EDUS04-906_b 4. Dimensions THE MARK (→) SHOWS PIPING DIRECTION REQUIRED SPACE 35-1/16(890) INCLUDING ( MOUNTING PLATE ) 10-13/16(275) 10-3/4(273) 8-1/4(209) GEAR CASE UNIT FIXED SCREWS (INSIDE PANEL) BOTTOM MULTI-COLORED INDICATOR LAMP/ INDOOR UNIT ON/OFF SWITCH TIMER LAMP OPERATING STATE ROOM TEMP. THERMISTOR GAS PIPE φ3/8(9.5)Cut TERMINAL BLOCK WITH EARTH TERMINAL 9/16(14.
EDUS04-906_b Wiring Diagrams 5. Wiring Diagrams FTXG09/12/15HVJU : PRINTED CIRCUIT BOARD : FLAME GROUND : FUSE : MULTI MONITOR : PILOT LAMP : LIMIT SWITCH FOR PANEL : LIMIT SWITCH FOR STREAMER : FAN MOTOR : SWING MOTOR : THERMISTOR : VARISTOR : CONNECTOR : OPERATION SWITCH : TERMINAL STRIP : SOLENOID VALVE : FERRITE CORE : PROTECTIVE GROUND CAUTION NOTE THAT OPERATION WILL RESTART AUTOMATICALLY IF THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK ON AGAIN.
Piping Diagrams EDUS04-906_b 6. Piping Diagrams FTXG09/12/15HVJU INDOOR UNIT 1/4(6.4)CuT SV SV HEAT EXCHANGER SOLENOID VALVE AT RATED VOLTAGE: CLOSED (UNDER DEHUMIDIFICATION OPERATION) THERMISTOR ON HEAT EXCH. CROSS FLOW FAN M HEAT EXCHANGER FAN MOTOR FIELD PIPING 1/ 4(6.4)CuT SINGLE UNION JOINT FIELD PIPING 3/8(9.5)CuT 3/8(9.5)CuT SINGLE UNION JOINT REFRIGERANT FLOW COOLING HEATING 4D061001 RXG09/12/15HVJU 9/32(7.0)CuT HEAT EXCHANGER 9/32(7.
EDUS04-906_b Capacity Tables 7. Capacity Tables 7.1 Heat Pump FTXG09HVJU + RXG09HVJU (60Hz 230V) Cooling AFR 11.9 BF 0.10 Temp: Celsius / TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) EWB EDB 20.0 25.0 °C °C TC SHC PI TC SHC PI TC SHC 30.0 PI TC SHC 32.0 PI TC SHC 35.0 PI TC SHC 40.0 PI 14.0 20 2.70 2.42 0.44 2.58 2.37 0.48 2.46 2.31 0.52 2.41 2.29 0.54 2.34 2.26 0.56 2.21 2.20 0.61 16.0 22 2.83 2.38 0.44 2.70 2.33 0.48 2.58 2.28 0.52 2.
Capacity Tables EDUS04-906_b Symbols AFR : Airflow rate Note: (m3/min.) BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. (°C) / (°F) TC : Total capacity (kW) / (kBtu/h) (°C) / (°F) SHC : Sensible heating capacity (kW) / (kBtu/h) PI : Power input (kW) 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat. 2. shows nominal (rated) capacities and power input. 3.
EDUS04-906_b Capacity Tables FTXG12HVJU + RXG12HVJU (60Hz 230V) Cooling AFR 13.0 BF 0.14 Temp: Celsius / TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) EWB EDB 20.0 25.0 °C °F TC SHC PI TC SHC PI TC SHC 30.0 PI TC SHC 32.0 PI TC SHC 35.0 PI TC SHC 40.0 PI 14.0 20 3.61 2.86 0.66 3.44 2.78 0.72 3.28 2.71 0.79 3.21 2.68 0.81 3.11 2.63 0.85 2.95 2.55 0.91 16.0 22 3.77 2.81 0.66 3.60 2.74 0.73 3.44 2.67 0.79 3.38 2.64 0.82 3.28 2.60 0.85 3.
Capacity Tables EDUS04-906_b Symbols AFR : Airflow rate Note: (m3/min.) BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. (°C) / (°F) TC : Total capacity (kW) / (kBtu/h) (°C) / (°F) SHC : Sensible heating capacity (kW) / (kBtu/h) PI : Power input (kW) 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat. 2. shows nominal (rated) capacities and power input. 3.
EDUS04-906_b Capacity Tables FTXG15HVJU + RXG15HVJU (60Hz 230V) Cooling AFR 13.8 BF 0.16 Temp: Celsius / TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) EWB EDB 20.0 25.0 °C °C TC SHC PI TC SHC PI TC SHC 30.0 PI TC SHC 32.0 PI TC SHC 35.0 PI TC SHC 40.0 PI 14.0 20 4.51 3.36 0.89 4.30 3.26 0.98 4.10 3.15 1.06 4.02 3.11 1.10 3.89 3.05 1.15 3.69 2.96 1.23 16.0 22 4.71 3.30 0.90 4.51 3.20 0.98 4.30 3.11 1.07 4.22 3.07 1.10 4.10 3.01 1.15 3.
Capacity Tables EDUS04-906_b Symbols AFR : Airflow rate Note: (m3/min.) BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. (°C) / (°F) TC : Total capacity (kW) / (kBtu/h) (°C) / (°F) SHC : Sensible heating capacity (kW) / (kBtu/h) PI : Power input (kW) 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat. 2. shows nominal (rated) capacities and power input. 3.
EDUS04-906_b Operation Limit 8. Operation Limit RXG09/12/15HVJU Heating Cooling 77 75 109 104 68 59 41 32 23 Continuous operation 50 Outdoor temp. (°FWB) 68 50 Pull-down period Continuous operation Outdoor temp. (°FDB) 86 32 14 5 14 -4 (-4°FDB) 50 59 68 73.4 77 82.4 86 Indoor temp. (°FWB) Notes: The graphs are based on the following conditions. • Equivalent piping length 25ft • Level difference 0ft • Air flow rate High Room Air Conditioners H-Series 50 68 Indoor temp.
Sound Level EDUS04-906_b 9. Sound Level 9.1 Measuring Location Indoor Unit 2.6ft 3.3ft (R5162) Outdoor Unit 3.3ft (R4796) Note: 1. Operation sound is measured in an anechoic chamber. 2. The data are based on the conditions shown in the table below. Cooling Heating Piping Length Indoor ; 80°FDB/67°FWB Outdoor ; 95°FDB/75°FWB Indoor ; 70°FDB/60°FWB Outdoor ; 47°FDB/43°FWB 16.
EDUS04-906_b Sound Level 9.2 Octave Band Level 9.2.1 Indoor Units FTXG09HVJU COOLING 70 OVER ALL ( dB ) NC-60 60 NC-50 SCALE 60Hz 208/230V (H) 60Hz 208/230V (L) A 42 26 ( B.G.
Sound Level 9.2.2 EDUS04-906_b Outdoor Units RXG09HVJU COOLING NC-60 60 NC-50 SCALE 60Hz 208-230V A 46 ( B.G.N IS ALREADY RECTIFIED ) 50 OPERATING CONDITIONS NC-40 POWER SOURCE 40 208-230V 60Hz JIS STANDARD (JIS9612) Cooling NC-30 30 NC-20 20 70 OVER ALL ( dB ) APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE 63 125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND SOUND PRESSURE LEVEL dB(0dB=0.0002μ bar) OCTAVE BAND SOUND PRESSURE LEVEL dB(0dB=0.
EDUS04-906_b Electric Characteristics 10. Electric Characteristics Representative Unit Combination Indoor Unit Outdoor Unit FTXG09HVJU RXG09HVJU FTXG12HVJU FTXG15HVJU RXG12HVJU RXG15HVJU Power Supply COMP Hz-Volts Voltage Range MCA MOP RHz 60-208 MAX. 60Hz 253V MIN. 60Hz 187V 14.5 15 29 60-230 60-208 60-230 60-208 60-230 MAX. 60Hz 253V MIN. 60Hz 187V MAX. 60Hz 253V MIN. 60Hz 187V 14.5 14.5 15 15 43 54 RLA 2.3 2.1 3.7 3.3 5.1 4.6 OFM IFM W FLA W 60 0.10 57 60 60 0.13 0.
Installation Manual EDUS04-906_b 11. Installation Manual 11.1 Indoor Units Read these SAFETY CONSIDERATIONS for Installation carefully before installing an air conditioner or heat pump. After completing the installation, make sure that the unit operates properly during the startup operation. Instruct the customer on how to operate and maintain the unit. Inform customers that they should store this Installation Manual with the Operation Manual for future reference.
EDUS04-906_b Installation Manual • Do not change the setting of the protection devices. If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Daikin are used, fire or explosion may occur. • Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps (inverter or rapid start types).
Installation Manual EDUS04-906_b Accessories 22 A Mounting plate 1 E Wireless remote controller 1 J Installation manual 1 B Deodorizing filter for streamer 1 F Remote controller holder 1 K Mounting plate fixing screws 3/16” × 1”L (M4 × 25mm) 9 C Titanium apatite photocatalytic air-purifying filter 1 G Dry batteries AAA.
EDUS04-906_b Installation Manual Indoor Unit Installation Drawings 1. Removing and installing indoor unit. • Installation method 1) Using the marks (3 locations) on top of the indoor unit, attach the A mounting plate hooks onto the indoor unit. 2) Attach the tabs on the bottom frame onto the A mounting plate. If the tabs are not hooked onto the plate, remove the front grille to hook them. (Check to see if the tabs are hooked securely.
Installation Manual EDUS04-906_b Installation Tips 1. Removing and installing front panel. Rotating shaft Rotating shaft • Removal method 1) Open the front panel. 2) Spread out the shaft hole on the left side and remove the rotating shaft. Spread out the shaft hole on the right side as well and remove the rotating shaft. Shaft hole Shaft hole • Installation method Insert the right and left rotating shafts on the front panel into the shaft holes one at a time and slowly close the panel.
EDUS04-906_b 4. Installation Manual Installing the titanium apatite photocatalytic air-purifying filter and deodorizing filter for streamer. 1) Open the front panel to pull out the air filter. 2) Attach the C titanium apatite photocatalytic airpurifying filter. 3) Attach the B deodorizing filter for streamer. 4) Replace the air filter to its original position and close the front panel. 5. How to replace the drain plug and drain hose.
Installation Manual EDUS04-906_b Indoor Unit Installation 1. Installing the mounting plate. • The A mounting plate should be installed on a wall which can support the weight of the indoor unit. 1) Temporarily secure the A mounting plate to the wall, make sure that the panel is completely level, and mark the boring points on the wall. 2) Secure the A mounting plate to the wall with screws.
EDUS04-906_b 4. Installation Manual Laying piping and wiring. • Lay the piping and drain hose according to the orientation of the piping coming out of the unit, as shown below. • Make sure the drain hose is sloped downward. • Wrap the piping and drain hose together using insulation tape. Piping bundle diagram Inter-unit wiring Gas pipe Drain hose Liquid pipe Insulation tape 4-1. Right-side, right-back, or right-bottom piping.
Installation Manual EDUS04-906_b Indoor Unit Installation 4-4. Wall embedded piping. Follow the instructions given under Left-side, left-back, or left-bottom piping . 1) Insert the drain hose to this depth so it won’t be pulled out of the drain pipe. Insert drain hose to this depth so it won’t be pulled out of drain pipe.
EDUS04-906_b 6. Installation Manual Connecting to the HA system. 1) Remove the front grille. (3 screws) 2) Remove the decelerator assembly parts. (1 screw) 2-1) Remove the decelerator assembly part screws. (See Fig. 1) 2-2) Remove the decelerator assembly part connector. Remove by pressing on the tabs on the bottom of the connector. (See the tab position diagram 1) 3) Remove the electric parts box. (1 screw, 2 tabs) 3-1) Remove the electric parts box fixing screw.
Installation Manual EDUS04-906_b Indoor Unit Installation 7. Drain piping. The drain hose should be inclined downward. 1) Connect the drain hose, as described right. No trap is permitted. Do not put the end of the hose in water. 3) When drain hose requires extension, obtain an extension hose commercially available. Be sure to thermally insulate the indoor section of the extension hose.
EDUS04-906_b Installation Manual Refrigerant Piping Work 1. Flaring the pipe end. (Cut exactly at right angles.) 1) Cut the pipe end with a pipe cutter. 2) Remove burrs with the cut surface facing downward so that the chips do not enter the pipe. 3) Put the flare nut on the pipe. 4) Flare the pipe. 5) Check that the flaring is properly made. Remove burrs Flaring Set exactly at the position shown below.
Installation Manual EDUS04-906_b Trial Operation and Testing 1. Trial operation and testing. 1-1. Measure the supply voltage and make sure that it falls in the specified range. 1-2. Trial operation should be carried out in either cooling or heating mode. • In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable temperature. 1) Trial operation may be disabled in either mode depending on the room temperature.
EDUS04-906_b 11.2 Installation Manual Outdoor Units Accessories Accessories supplied with the outdoor unit: (A) Installation manual 1 (C) Binding band 1 (B) Drain plug (Heat pump-Models) There is on the bottom packing case. 1 Precautions for Selecting the Location 1) Choose a place strong enough to bear the weight and vibration of the unit, The location should not amplified the unit noise.
Installation Manual EDUS04-906_b Precautions on Installation • Ensure the strength and level of the installation will not cause any operating vibration or noise after installed. • In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare four sets of 3/8 inch (M10) or 7/16 inch (M12) foundation bolts, nuts and washers each which are available on the market.
EDUS04-906_b Installation Manual Outdoor Unit Installation (1) 1. Installing outdoor unit. 1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation Drawings”. 2) If drain work is necessary, follow the procedures below. 2. Drain work (heat pump-models). 1) Use drain plug for drainage.
Installation Manual EDUS04-906_b Outdoor Unit Installation (2) 5. Purging air and checking gas leakage. • When piping work is completed, it is necessary to purge the air and check for gas leakage. WARNING 1) 2) 3) 4) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle. When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
EDUS04-906_b Installation Manual Outdoor Unit Installation (3) 6. Refilling the refrigerant. Check the type of refrigerant to be used on the machine nameplate. Precautions when adding R410A Fill from the liquid pipe in liquid form. It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation. 1) Before filling, check whether the cylinder has a siphon attached or not.
Installation Manual EDUS04-906_b Wiring (1) WARNING 1) Do not use spliced wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire. Follow all Local, and State electrical codes. 2) Do not use locally purchased electrical parts inside the product. (Do not overload the circuit by adding drain pump or other electrical equipment to unit terminals.) Doing so may cause electric shock or fire. 3) Be sure to install an earth leak detector.
EDUS04-906_b Installation Manual Wiring (2) CAUTION (1) In case using stranded wires is unavoidable for some reason, make sure to install the round crimp-style terminals on the tip. Round crimp-style terminal Stranded wire Place the round crimp-style terminals on the wires up to the covered part and secure in place. Screw 1) Use the following method when installing a single core wire.
Operation Manual EDUS04-906_b 12. Operation Manual Read these SAFETY CONSIDERATIONS for Operations carefully before operating an air conditioner or heat pump. Make sure that the unit operates properly during the startup operation. Instruct the customer on how to operate and maintain the unit. Inform customers that they should store this Operation Manual with the Installation Manual for future reference.
EDUS04-906_b • Placing a flower vase or other containers with water or other liquids on the unit could cause a shock or fire if a spill occurs. • Do not touch the air outlet or horizontal blades while the swing flap is in operation because fingers could get caught and injured. • Never touch the internal parts of the controller. Do not remove the front panel because some parts inside are dangerous to touch. To check and adjust internal parts, contact your dealer.
Operation Manual EDUS04-906_b • Pay Attention to Operating Sound. Be sure to use the following places: a. Places that can sufficiently withstand the weight of the air conditioner or heat pump yet can suppress the operating sound and vibration. b. Places where warm air from the air outlet of the outside unit or the operating sound of the outside unit does not annoy neighbors. • Make sure that there are no obstacles close to the outside unit.
EDUS04-906_b Operation Manual QUATERNITY DRYING / DRY COOLING...................
Operation Manual EDUS04-906_b Ground terminal 44 Room Air Conditioners H-Series
EDUS04-906_b Operation Manual DRY button Room Air Conditioners H-Series 45
Operation Manual 46 EDUS04-906_b Room Air Conditioners H-Series
EDUS04-906_b Room Air Conditioners H-Series Operation Manual 47
Operation Manual 48 EDUS04-906_b Room Air Conditioners H-Series
EDUS04-906_b Operation Manual COOLING • DRY Operation “DRY COOLING” Operation DRY operation Hi Std Lo Constant Note on “Dry Cooling” operation “DRY COOLING” may raise humidity temporarily. Note on Dry Operation The operation mode change from COOLING to DRY may raise humidity temporarily.
Operation Manual 50 EDUS04-906_b Room Air Conditioners H-Series
EDUS04-906_b Room Air Conditioners H-Series Operation Manual 51
Operation Manual 52 EDUS04-906_b Room Air Conditioners H-Series
EDUS04-906_b Operation Manual COOLING or “DRY COOLING” operation, the A) FLASH STEAMER AIR PURIFYING individual operation B) “DRY COOLING” • COOLING C) HEATING Room Air Conditioners H-Series 53
Operation Manual EDUS04-906_b COOLING BREEZE operation is for COOLING, “DRY COOLING” AND FLASH STREAMER, AIR PURIFYING operation.
EDUS04-906_b Room Air Conditioners H-Series Operation Manual 55
Operation Manual EDUS04-906_b -1.8°F (-1°C) -3.
EDUS04-906_b Room Air Conditioners H-Series Operation Manual 57
Operation Manual EDUS04-906_b COOLING or “DRY COOLING” mode or 58 Room Air Conditioners H-Series
EDUS04-906_b Room Air Conditioners H-Series Operation Manual 59
Operation Manual 60 EDUS04-906_b Room Air Conditioners H-Series
EDUS04-906_b Room Air Conditioners H-Series Operation Manual 61
Operation Manual 62 EDUS04-906_b Room Air Conditioners H-Series
EDUS04-906_b Room Air Conditioners H-Series Operation Manual 63
Operation Manual 64 EDUS04-906_b Room Air Conditioners H-Series
EDUS04-906_b Room Air Conditioners H-Series Operation Manual 65
Operation Manual 66 EDUS04-906_b Room Air Conditioners H-Series
EDUS04-906_b Room Air Conditioners H-Series Operation Manual 67
Operation Manual 68 EDUS04-906_b Room Air Conditioners H-Series
EDUS04-906_b Room Air Conditioners H-Series Operation Manual 69
Operation Manual EDUS04-906_b 3P226009-1 70 Room Air Conditioners H-Series
EDUS04-906_b Optional Accessories 13. Optional Accessories 13.1 Option List 13.1.
Optional Accessories 13.2 EDUS04-906_b Installation Manual 13.2.1 KRP413A1S Safety Precautions Read these safety precautions carefully before installing the unit, and be sure to install the unit properly. This manual classifies precautions to the user into the following two categories. These warnings and cautions are for your safety. Follow them.
EDUS04-906_b Optional Accessories Installation This product is available in two types. The KRP413A1S · KRP413AA1S is for installation in a case independent of the indoor unit, and the KRP413A1 is for installation within the indoor unit. 1. KRP413A1S · KRP413AA1S 1 3. Attaching Adaptor Case Assy (for KRP413A1S · KRP413AA1S) Installation diagram 1 Adaptor case Indoor unit PCB Using the screws (to mount on a wall, etc.) Use the 3 supplied screws to attach the case assy .
Optional Accessories EDUS04-906_b Wiring 1. Wiring 4. Connection with Remote Controller Connect one end of the wiring to connector S21 of the PCB in the indoor unit. Connect the other end of the wiring to connector S6 of the adaptor PCB. Connect field wiring according to the functions assigned to each connection terminal of the adaptor PCB. Secure all wires. 1 Example connections with three kinds of remote controllers are shown bellow. Note: These connections cannot be used in combination.
EDUS04-906_b Optional Accessories Test Operation and Confirmation 1. When the System is Not Working Is the air conditioner working properly? Are the connectors of the wiring properly connected? Are the remote controller and field wiring properly connected? Are all switch settings correct? If there is nothing apparently wrong, conduct a diagnostic check using the following procedure. Diagnostic check Defect in adaptor PCB. Defect in wiring. Defect in indoor unit’s PCB.
Optional Accessories EDUS04-906_b 13.2.2 KRP928B2S 1.Overview, Features and Compatible Models Safety Precautions This kit is the interface required when connecting the central controller and a Daikin Room Air Conditioner. Use of the central controller makes it possible to perform the following monitoring and operations. It is compatible with room air conditioners which have an HA connector S21. Read these Safety Precautions carefully to ensure correct installation.
EDUS04-906_b Optional Accessories 5.Control Codes Tu rn the power on after all the switches have been set. Settings made while the power is on are invalid. When using a central remote controller, the operating codes can be used to limit operation from wireless remote controllers. : permitted; ´ : prohibited OFF (Factory setting) Overseas ON “Automatic” operation is available from the central controller.
Optional Accessories EDUS04-906_b 13.2.3 KPW937A4 Before Installation Checking the parts Check the following parts Name Louver Installation manual Shape Quantity With 4 screws 1piece 1piece Installation Procedure Selection of Installation Location Use when installing in a location that meets the following conditions. When installing near the border to a neighbor's house If exhaust blows directly on passers-by because outdoor unit is installed facing a road.
Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms tot he applicable standards, and is suitable for use, in the region where the product will be used.