SiUS39-601 Troubleshooting by Indication on the Remote Controller
Troubleshooting 187
Troubleshooting
The number of indoor units that can be connected to a single outdoor unit system depends on the
type of outdoor unit.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2827)
The total
of indoor units
displaying "UA" and
indoor units connected to the
same refrigerant system is
within connectable
number of
unit
Normal
NO
NO
There are too many indoor units
within the same refrigerant
system.
Push and hold the RESET
button on the outdoor unit
PC board for 5 seconds.
YES
Is the outdoor
PC board replaced
to spare parts PC
board ?
YES
The setting after replacing spare
PC board has not been set yet.
Please set as per page 73.
NO
YES
Does a malfunction occur?
Replace outdoor unit PC board
(A1P).