Installation manual
3 ■English
Indoor/Outdoor Unit 
Installation Drawings
For installation of the indoor units, refer to the installation manual which was provided with the units.
(The diagram shows a wall-mounted indoor unit.)
 CAUTION
1) Do not connect the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the 
indoor unit in order to add another indoor unit later.
Make sure no dirt or moisture gets into either side of the embedded branch piping.
See “7 Refrigerant piping work” on page 8 for details.
2) Heat pump type: It is impossible to connect the indoor unit for one room only. Be sure to connect at least 2 rooms.
Cooling only type: It is possible to connect the indoor unit for one room only.
Cut thermal insulation 
pipe to an appropriate 
length and wrap it with 
tape, making sure that no 
gap is left in the insulation 
pipe’s cut line.
Wrap the insulation 
pipe with the finishing 
tape from bottom to top.
Caulk 
pipe hole 
gap 
with putty. 
(Foot bolt-hole centres)
58cm
(Foot bolt-hole 
 centres)
33cm
25cm from wall
Allow space for piping 
and electrical servicing.
Allow 30cm of work 
space below the 
ceiling surface.
If there is the danger of the unit falling 
or overturning, fix the unit with 
foundation bolts, or with wire or other 
means.
If the location does not have good 
drainage, place the unit on a level 
mounting base (or a plastic pedestal). 
Install the outdoor unit in a level 
position. Failure to do so may result in 
water leakage or accumulation.
Level mounting base 
(available separately)
Clamping material
Insulation tube
Service lid
Tape
Also insulate the connection on the outdoor unit.
Use tape or insulating material on all connections 
to prevent air from getting in between the copper 
piping and the insulation tube.
Be sure to do this if the outdoor unit is installed 
above.
Stop valve cover
01_EN_3P164392-2H.fm Page 3 Friday, March 16, 2007 4:26 PM










