Specifications
Specifications SiUS39-602
18 Specifications
Ceiling Suspended Type
Notes: ★
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping: 25ft (Horizontal)
★
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
★
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Model FXHQ12MVJU FXHQ24MVJU FXHQ36MVJU
★
1 Cooling Capacity Btu/h 12,000 24,000 36,000
★
2 Heating Capacity Btu/h 13,500 27,000 40,000
Casing Color White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5)
Dimensions: (H×W×D) in 7-11/16×37-13/16×26-3/4 7-11/16×55-1/8×26-3/4 7-11/16×62-5/8×26-3/4
Coil (Cross
Fin Coil)
Rows × Stages × FPI 2×12×15 3×12×15 2×12×15+2×10×15
Face Area ft² 1.96 3.15 3.66+2.95
Fan
Model 3D12K1AA1 3D12K2AA1 3D12K2AA1
Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output W 62 130 130
Air Flow Rate (H/L) CFM 410/340 710/600 830/670
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material Glass Wool Glass Wool Glass Wool
Air Filter Resin Net (with Mold Resistant) Resin Net (with Mold Resistant) Resin Net (with Mold Resistant)
Piping
Connections
Liquid Pipes in
φ
1/4 (Flare Connection)
φ
3/8 (Flare Connection)
φ
3/8 (Flare Connection)
Gas Pipes in
φ
1/2 (Flare Connection)
φ
5/8 (Flare Connection)
φ
5/8 (Flare Connection)
Drain Pipe in
VP20
(External Dia. 1, Internal Dia. 3/4)
VP20
(External Dia. 1, Internal Dia. 3/4)
VP20
(External Dia. 1, Internal Dia. 3/4)
Machine Weight (Mass) Lbs 55 80 90
★
4 Sound Level (H) dBA 42 44 46
Safety Devices
Fuse
Thermal Protector for Fan Motor
Fuse
Thermal Protector for Fan Motor
Fuse
Thermal Protector for Fan Motor
Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Connectable Outdoor Unit R-410A Series R-410A Series R-410A Series
Standard Accessories
Operation Manual, Installation
Manual, Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
Operation Manual, Installation
Manual, Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
Operation Manual, Installation
Manual, Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
Drawing No. 4D049326