Specifications

SiUS39-602 Specifications
Specifications 23
1.3 BS Units
Notes:
1 If the total capacity of all indoor units connected to the system is less than 24,000 Btu/h, connect the
attached pipe to the field pipe.
(Braze the connection between the attached pipe and field pipe.)
Connection Range for BS Unit
Model BSVQ36MVJU BSVQ60MVJU
Power Supply 60Hz 208~230V 60Hz 208~230V
Total Capacity Index of Connectable Indoor
Unit
Less than 36 Less than 60
No. of Connectable Indoor Units Max. 3 Max. 5
Casing Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) in 7-1/4
×
12-1/4
×
11 7-1/4
×
12-1/4
×
11
Sound Absorbing Thermal Insulation
Material
Flame and Heat Resistant Foamed Polyethylene Flame and Heat Resistant Foamed Polyethylene
Piping
Connection
Indoor
Unit
Liquid Pipes
φ
3/8 (Flare Connection)
1
φ
3/8 (Flare Connection)
Gas Pipes
φ
5/8 (Flare Connection)
1
φ
5/8 (Flare Connection)
Outdoor
Unit
Liquid Pipes
φ
3/8 (Flare Connection)
1
φ
3/8 (Flare Connection)
Suction Gas Pipes
φ
5/8 (Flare Connection)
1
φ
5/8 (Flare Connection)
Discharge Gas
Pipes
φ
1/2 (Flare Connection)
1
φ
1/2 (Flare Connection)
Machine Weight (Mass) Lbs 18 18
Standard Accessories
Installation Manual, Attached Pipe, Insulation pipe cover,
Clamps
Installation Manual, Insulation pipe cover, Clamps
Drawing No. 4D045334 4D045339
Components
Outdoor unit/BS unit
model name
Total capacity of connectable
indoor units
Number of connectable
indoor units
Indoor unit total capacity
REYQ72M 50.5~93.5 12
Same number of
BS units
REYQ96M 67.5~124.5 16
REYQ144M 101~187 20
REYQ168M 118~218 20
REYQ192M 134.5~249.5 20