Specifications

Basic Control SiUS39-602
42 Function
Compressor Operating Priority
INV: Inverter compressor
STD1: Standard compressor 1
Each compressor operates in the following order of priority.
REYQ72M
INV STD1
No. 1 No. 2
REYQ96M
INV STD1
No. 1 No. 2
REYQ72M
STEP INV STD1
1 52Hz OFF
2 57Hz OFF
3 62Hz OFF
4 68Hz OFF
5 74Hz OFF
6 81Hz OFF
7 88Hz OFF
8 96Hz OFF
9 104Hz OFF
10 110Hz OFF
11 116Hz OFF
12 124Hz OFF
13 133Hz OFF
14 143Hz OFF
15 158Hz OFF
16 165Hz OFF
17 177Hz OFF
18 189Hz OFF
19 202Hz OFF
20 210Hz OFF
21 52Hz ON
22 74Hz ON
23 96Hz ON
24 116Hz ON
25 133Hz ON
26 158Hz ON
27 177Hz ON
28 202Hz ON
29 210Hz ON
Compressors are operated in the order of descending priorities.
Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
Master unit”, and “slave unit” in this section are the names for control, and they will be transferred according to the
priority of rotation system.
REYQ96M
STEP INV STD1
152HzOFF
257HzOFF
362HzOFF
468HzOFF
574HzOFF
681HzOFF
788HzOFF
896HzOFF
9104HzOFF
10 110Hz OFF
11 116Hz OFF
12 124Hz OFF
13 133Hz OFF
14 143Hz OFF
15 158Hz OFF
16 165Hz OFF
17 177Hz OFF
18 189Hz OFF
19 202Hz OFF
20 210Hz OFF
21 52Hz ON
22 74Hz ON
23 96Hz ON
24 116Hz ON
25 133Hz ON
26 158Hz ON
27 177Hz ON
28 202Hz ON
29 210Hz ON