Specifications

SiUS39-602 Special Control
Function 49
3.1.2 Startup Control in Heating Operation
Note: ON at starting immediately after power is on.
Actuator
Pressure equalization
before start-up
Starting control
Step1 Step2
Compressor OFF 52Hz + OFF 52Hz + OFF
Outdoor unit fan STEP 4 STEP 7 STEP 7
Four way valve 1 ON ON ON
Four way valve 2 Hold Hold OFF
Main motorized valve (EV1) 0 pls 180 pls 180 pls
Sub motorized valve (EV2) 0 pls 0 pls 1000 pls
Sub-cooling motorized valve (EV3) 0 pls 0 pls 0 pls
Hot gas bypass valve (SVP) OFF ON ON
Oil equalization valve (SVO) OFF OFF OFF
Receiver gas charging valve (SVL) OFF ON ON OFF
Receiver gas discharge valve (SVG) OFF OFF OFF ON
Discharge pipe stop valve (SVR) Hold ON OFF ON
Non-operating unit liquid pipe stop
valve (SVSL)
ON ON ON
High pressure gas pipe pressure
reduction valve (SVC)
Hold
*Note
OFF OFF
Ending conditions 1 min. 5 sec.
230 sec.
Pc - Pe > 58 psi
or