Performance
Cooling (Btu/hr)
Rated (Min/Max)
10,900 (4,400 / 13,300)
Sensible @ AHRI
9,480
Moisture Removal gal/h
.45
Operating Range
50°F 115°F
Rated Cooling Conditions:
Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
Submittal Data Sheet
FTK12NMVJU / RK12NMVJU
Efficiency
Cooling
SEER
19
EER
12.5
Electrical
208/60/1
230/60/1
System MCA
12.2
12.2
System MFA
15
15
Compressor RLA
7.5
7.5
Outdoor fan motor FLA
.15
.15
Outdoor fan motor W
18
18
Indoor fan motor FLA
.23
.23
Indoor fan motor W
28
28
MFA: Max. fuse amps MCA: Min. circuit amps (A) FLA: Full load amps (A)
RLA: Rated load amps (A) W: Fan motor rated output (W)
Piping
Liquid (in)
1/4
Gas (in)
3/8
Drain (in)
5/8
Max. Interunit Piping Length (ft)
65.625
Max. Interunit Height Difference (ft)
49.25
Chargeless (ft)
32.8
Additional Charge of Refrigerant (oz/ft)
.21
Indoor Specifications
Airflow Rate (cfm)
Cooling
H
M
434
311
L
SL
247
145
Sound (dBA)
H / M / L / SL
45 / 37 / 30 / 19
Dimensions (H × W × D) (in)
11-1/4 × 30-5/16 × 8-3/4
Weight (Lbs)
18
Outdoor Specifications
Compressor
Hermetically Sealed Swing Type
Refrigerant
R-410A
Refrigerant Oil
PVE (FVC50K)
Airflow Rate (cfm)
Cooling
H
1,105
SL
865
Sound Power Level (dBA)
49
Dimensions (H × W × D) (in)
21-5/8 × 26-9/16 × 11-3/16
Weight (Lbs)
60
Job Name:
Tag#
Complete warranty details available from your local dealer or at
www.daikincomfort.com. To receive the 12-Year Parts Limited
Warranty, online registration must be completed within 60 days of
installation. Online registration is not required in California or Quebec.
If product is installed in a commercial application, limited warranty
period is 5 years.

Summary of content (4 pages)