117 Appendix
3. Operation Limit
RK30/36NMVJU
RX30/36NMVJU
Cooling
114.8
104
Outdoor temp. (˚FDB)
Pull-down period
Continuous operation
14
32
50
*NOTE 2
68
86
122
57.2 68 73.4 82.4 8650
Indoor temp. (˚FWB)
25ft
0ft
High
4D108219
Notes:
1. The graphs are based on the following conditions.
Equivalent piping length
Level difference
Airflow rate
2. Facility Setting (cooling at low outdoor temperature)
This function is limited only for facilities
(the target of air conditioning is equipment such as computer).
Never use it in a residence or office (the space where is a human).
Refer to the installation manual in detail of setting.
Heating
Cooling
Outdoor temp. (˚FDB)
Pull-down period
Continuous operation
Outdoor temp. (˚FWB)
Continuous operation
50 57.2 68 73.4 82.4 86
Indoor temp. (˚FWB)
50 68 86
Notes:
Indoor temp. (˚FDB)
(5˚FDB)
1. The graphs are based
on the following conditions.
Equivalent piping length
Level difference
Airflow rate
25ft
0ft
High
2. Facility Setting (cooling at low outdoor temperature)
This function is limited only for facilities (the target of air conditioning is equipment such as computer).
Never use it in a residence or office (the space where is a human).
Refer to the installation manual in detail of setting.