37 Functions and Control
3.3.4 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning it off.
(The function is not activated when defrosting.)
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not activated when defrosting.)
RK30/36NMVJU RX30/36NMVJU
Cooling Heating Cooling Heating
A (Hz) 28 28 30
B (Hz) 42 42 78
C (Hz) 56 56 118
D (seconds) 180 180 1080
E (seconds) 180 180 90
F (seconds) 180 180 240
(sec.)
Time
(R13528)
(Hz)
Frequency
C
B
DEF
A