Service Manual

SiUS041638E Troubleshooting
Service Diagnosis 78
4.16 Discharge Pipe Temperature Control
Error Code
F3
Method of Error
Detection
An error is determined with the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above A, the compressor
stops.
The error is cleared when the discharge pipe temperature has dropped below B.
RK(X)30/36NMVJU
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Troubleshooting
Check No.01
Refer to P.92
Check No.12
Refer to P.94
Check No.14
Refer to P.95
AB
°C °F °C °F
120 248 107 224.6
(R20417)
Caution
NG
OK
OK
OK
NG
NG
Discharge pipe thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
Refrigerant shortage
Four way valve
Water mixed
Stop valve
Check No. 12
Check the electronic
expansion valve.
Replace the defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.