EDUS181520C Electric Characteristics
Multi-Split Type Air Conditioners RMXS-L Series 83
2
11.Electric Characteristics
C: 3D080740
Outdoor Unit
Power Supply Compressor OFM
Hz Volts Min. Max. MCA MOP MSC RLA W FLA
RMXS48LVJU 60
208 187 229
27.0 30
23.7 22.7
70
+
70
0.3
+
0.3
230 207 253 21.5 20.5
Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Cooling:
Indoor temp.: 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB)
Outdoor temp.: 95°FDB (35°CDB)
Heating:
Indoor temp.: 70°FDB (21°CDB)
Outdoor temp.: 47°FDB (8.3°CDB) / 43°FWB (6°CWB)
2. Voltage range.
Units are suitable for use on electrical systems where voltage
supplied to unit terminal is not below or above listed range limits.
3. Maximum allowable voltage variation between phases is 2%.
4. MCA represents maximum input current.
5. MOP represents capacity which may accept MCA.
6. Select wire size based on the value of MCA.
7. MOP is used to select the fuse, circuit breaker, or the ground
fault circuit interrupter (earth leakage circuit breaker).
8. Be sure to install a ground leak detector.
(This unit uses an inverter, which means that a ground leak
detector capable of handling high harmonics must be used in
order to prevent malfunctioning of the ground leak detector.)
MOP : Max. overcurrent protective device (A)
MSC : Max. current while starting compressor (A)
RLA : Rated load amps (A)
OFM : Outdoor fan motor
W : Fan motor rated output (W)
FLA : Full load amps (A)
The relationship between the starting time and the starting current.
MSC
Starting time
RLA
Starting current