Si34-704 Other Control
Function 115
5.3 Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting” or “Demand 2 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adapter is required.
Set item Condition Content
Demand 1 Mode 1 The compressor operates at approx. 60% or less of rating.
Mode 2 The compressor operates at approx. 70% or less of rating.
Mode 3 The compressor operates at approx. 80% or less of rating.
Demand 2 The compressor operates at approx. 40% or less of rating.