Outline of Control (Indoor Unit) Si34-704
124 Function
6.9 Control of Outdoor Air Processing Unit
(Unique Control for Outdoor Air Processing Unit)
6.9.1 Selection of Operation Mode (by suction air thermostat)
Objective To select cooling, heating, or fan operation mode according to the suction air (outdoor air)
temperature.
Details [Outdoor air processing unit]
–5 5 15 19
18
43
Suction temperature (T1) ºC
Cooling mode
Fan operation (with thermostat OFF)
Cooling
Cooling
"Low outdoor air protection control"
Fan stop
Fan operation