Field Setting Si34-704
160 Test Operation
“Detail of DS1-1~4, DS2-1~4 setting” (for Overseas general)
Unit Setting method ( represents the position of switches)
Cooling Only (5HP)
RXQ5PY1
Set DS2-1 to ON.
Cooling Only (8HP)
RXQ8PY1
Set DS2-1 and DS2-3 to ON.
Cooling Only (10HP)
RXQ10PY1
Set DS2-1, DS2-2 and DS2-3
to ON.
Cooling Only (12HP)
RXQ12PY1
Set DS2-1 and DS2-4 to ON.
Cooling Only (14HP)
RXQ14PY1
Set DS2-1, DS2-2 and DS2-4
to ON.
Cooling Only (16HP)
RXQ16PY1
Set DS2-1, DS2-3 and DS2-4
to ON.
Cooling Only (18HP)
RXQ18PY1
Set DS2-1, DS2-2, DS2-3, and DS2-4
to ON.