Field Setting Si34-704
174 Test Operation
{
: ON
z
: OFF
9
: Blink
c
de
Setting
No.
Setting
contents
Setting No. indication Setting No. indication Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12
External
low noise /
Demand
setting
{zzzzzz{z z { { z z
NO
(Factory
setting)
{zzzzz
9
YES
{zzzz
9
z
22 Night-time
low noise
setting
{ z { z { { z
OFF
(Factory
setting)
{zzzzz z
Mode 1
{zzzzz
9
Mode 2
{zzzz
9
z
Mode 3
{zzzz
9 9
25 External
low noise
setting
{ z { { z z {
Mode 1
{zzzz z
9
Mode 2
(Factory
setting)
{zzzz
9
z
Mode 3
{zzz
9
z z
26 Night-time
low noise
start setting
{ z { { z { z
PM 8:00
{zzzz z
9
PM 10:00
(Factory
setting)
{zzzz
9
z
PM 0:00
{zzz
9
z z
27 Night-time
low noise
end setting
{ z { { z { {
AM 6:00
{zzzz z
9
AM 7:00
{zzzz
9
z
AM 8:00
(Factory
setting)
{zzz
9
z z
29 Capacity
precedence
setting
{ z { { { z {
Low noise
precedence
(Factory
setting)
{zzzzz
9
Capacity
precedence
{zzzz
9
z
30 Demand
setting 1
{ z { { { { z
60 % of
rated power
consumption
{zzzz z
9
70 % of
rated power
consumption
(Factory
setting)
{zzzz
9
z
80 % of
rated power
consumption
{zzz
9
z z
32
Normal
demand
setting
{ z z z z z z
OFF
(Factory
setting)
{zzzzz
9
ON
{zzzz
9
z
Setting mode indication section Setting No. indication section Set contents indication section