Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 205
3.6
“
A9
”
Electronic Expansion Valve Malfunction / Dust
Clogging
Remote
Controller
Display
A9
Applicable
Models
FXFQ25~125M
Method of
Malfunction
Detection
Check coil condition of electronic expansion valve by using microcomputer.
Check dust clogging condition of electronic expansion valve main body by using
microcomputer.
Malfunction
Decision
Conditions
Pin input for electronic expansion valve coil is abnormal when initializing microcomputer.
Either of the following conditions is seen/caused/ occurs while the unit stops operation.
z
Temperature of suction air (R1T) – temperature of liquid pipe of heat exchanger (R2T)>8°C.
z
Temperature of liquid pipe of heat exchanger (R2T) shows fixed degrees or below.
Supposed
Causes
Defective drive of electronic expansion valve
Defective PCB of indoor unit
Defective relay cables