Troubleshooting by Indication on the Remote Controller Si34-704
216 Troubleshooting
3.14
“
E1
”
Outdoor Unit: PC Board Defect
Remote
Controller
Display
E1
Applicable
Models
RXQ5P~54P
Method of
Malfunction
Detection
Check data from E²PROM
Malfunction
Decision
Conditions
When data could not be correctly received from the E²PROM
E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned off.
Supposed
Causes
Defect of outdoor unit PC board (A1P)
Defective connection of inside/ outside relay wires
Troubleshooting
Turn off the power once and
turn on again.
Return to normal?
Check if inside/
outside relay wires of
outdoor main PCB is
disconnected.
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
External factor other than
malfunction (for example,
noise etc.).
Connect the inside/ outside
relay wires correctly.
Replace outdoor main PCB
(A1P).
(V3064)
NO
NO
YES