Specifications

Troubleshooting by Indication on the Remote Controller Si34-704
236 Troubleshooting
3.26
J3
Outdoor Unit: Malfunction of Discharge Pipe
Thermistor (R3, R31, 32T)
Remote
Controller
Display
J3
Applicable
Models
RXQ5P~54P
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by discharge pipe temperature
thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Supposed
Causes
Defect of thermistor (R31T, R32T) for outdoor unit discharge pipe
Defect of outdoor unit PC board (A1P)
Defect of thermistor connection