Troubleshooting by Indication on the Remote Controller Si34-704
240 Troubleshooting
3.29
“
J7
”
Outdoor Unit: Malfunction of Liquid Pipe Thermistor 1
(R6T)
Remote
Controller
Display
J7
Applicable
Models
RXQ5P~54P
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by liquid pipe thermistor.
Malfunction
Decision
Conditions
When the liquid pipe thermistor is short circuited or open.
Supposed
Causes
Faulty liquid pipe thermistor 1 (R6T)
Faulty outdoor unit PC board
Defect of thermistor connection