Specifications

RXYQQ8~20T7Y1B
VRV IV System Air Conditioner
4P345099-1 – 2013.04
Installation and operation manual
21
10.4.6. Vacuum drying
To remove all moisture from the system, proceed as follows:
1 Evacuate the system for at least 2 hours to a target vacuum of
–100.7 kPa.
2 Check that, with the vacuum pump turned off, the target vacuum
is maintained for at least 1 hour.
3 Should you fail to reach the target vacuum within 2 hours or
maintain the vacuum for 1 hour, the system may contain too
much moisture.
4 In that case, break the vacuum by pressurizing with nitrogen gas
to a gauge pressure of 0.05 MPa (0.5 bar) and repeat steps 1 to
3 until all moisture has been removed.
5 The outdoor stop valves can now be opened, and/or additional
refrigerant can be charged (see "14.4. Method for adding
refrigerant" on page 32).
11. Pipe insulation
After finishing the leak test and vacuum drying, the piping must be
insulated. Take into account the following points:
Make sure to insulate the connection piping and refrigerant
branch kits entirely.
Be sure to insulate the liquid and gas piping (for all units).
Use heat resistant polyethylene foam which can withstand a
temperature of 70°C for liquid piping and polyethylene foam
which can withstand a temperature of 120°C for gas piping.
Reinforce the insulation on the refrigerant piping according to
the installation environment.
Condensation might form on the surface of the insulation.
If there is a possibility that condensation on the stop valve might
drip down into the indoor unit through gaps in the insulation and
piping because the outdoor unit is located higher than the indoor
unit, this must be prevented by sealing up the connections. See
below figure.
1 Insulation material
2 Caulking etc.
12. Electrical wiring work
12.1. Precautions on electrical wiring work
For the existing power supply and transmission wiring, check that the
specifications match the requirements as described in this chapter
and that other parts (especially terminals) do not appear to have
deteriorated. Implement appropriate procedures (e.g., replacement) if
required.
NOTICE
Make sure to use a recommended bubble test solution
from your wholesaler. Do not use soap water, which may
cause cracking of flare nuts (soap water may contain salt,
which absorbs moisture that will freeze when the piping
gets cold), and/or lead to corrosion of flared joints (soap
water may contain ammonia which causes a corrosive
effect between the brass flare nut and the copper flare.
INFORMATION
After opening the stop valve, it is possible that the pressure
in the refrigerant piping does not rise. This might be
caused by e.g., the closed state of the expansion valve in
the outdoor unit circuit, but does not present any problem
for correct operation of the unit.
NOTICE
The connections to the indoor units and all indoor units
should also be leak and vacuum tested. Keep, if existing,
all (field supplied) field valves to the indoor units open as
well.
Leak test and vacuum drying should be done before the
power supply is set to the unit. If not, see "10.4. Leak test
and vacuum drying" on page 19 for more information.
Ambient temperature Humidity Minimum thickness
30°C 75% to 80% RH 15 mm
>30°C 80% RH 20 mm
WARNING
Electrical installation. All field wiring and components must
be installed by a licensed electrician and must comply with
the applicable legislation.
NOTICE
Electrical wiring work recommendations. To persons in
charge of electrical wiring work: Do not operate the unit
until the refrigerant piping is complete. "10.4. Leak test and
vacuum drying" on page 19. Running the unit before the
piping is ready will break the compressor.
DANGER: Electrical shock
See "2. General safety precautions" on page 2.
2
1