Specifications

RXYQQ8~20T7Y1B
VRV IV System Air Conditioner
4P345099-1 – 2013.04
Installation and operation manual
39
[2-25]= Low noise operation level via the external control
adaptor
If the system needs to be running under low noise
operation conditions when an external signal is sent to
the unit, this setting defines the level of low noise that
will be applied (3: Level 3<2: Level 2<1: Level 1).
This setting will only be effective when the optional
external control adaptor (DTA104A61/62) is installed
and the setting [2-12] was activated.
Default value=2.
To activate function change [2-25]=1, 2 or 3.
[2-26]= Low noise operation start time
Change [2-26]=1, 2 or 3 in function of required timing.
Default value=2.
This setting is used in conjunction with setting [2-22].
[2-27]= Low noise operation stop time
Default value=3.
This setting is used in conjunction with setting [2-22].
[2-30]= Power consumption limitation level (step 1) via the
external control adaptor (DTA104A61/62).
If the system needs to be running under power
consumption limitation conditions when an external
signal is sent to the unit, this setting defines the level
power consumption limitation that will be applied for
step1. The level is according to the table.
Default value=3.
Change [2-30]=1, 2, 3, 4, 5, 6, 7 or 8 in function of
required limitation.
Value
[2-26]
Start time automatic low noise
operation (approximately)
1 20h00
2 22h00 (default)
3 24h00
Value
[2-27]
Stop time automatic low noise
operation (approximately)
16h00
27h00
3 8h00 (default)
Value
[2-30]
Power consumption limitation
(approximately)
160%
265%
3 70% (default)
475%
580%
685%
790%
895%
[2-31]= Power consumption limitation level (step 2) via the
external control adaptor (DTA104A61/62).
If the system needs to be running under power
consumption limitation conditions when an external
signal is sent to the unit, this setting defines the level
power consumption limitation that will be applied for
step2. The level is according to the table.
Default value=1.
Change [2-31]=1, 2 or 3 in function of required
limitation.
[2-32]= Forced, all time, power consumption limitation operation
(no external control adaptor is required to perform
power consumption limitation).
If the system always needs to be running under power
consumption limitation conditions, this setting activates
and defines the level power consumption limitation that
will be applied continuously. The level is according to
the table.
Default value=0 (OFF).
Change [2-32]=0, 1 or 2 in function of required
limitation.
[2-73]= When the system is using non-R410A VRV DX indoor
units, the system needs to get the proper input
according to the table below.
Default value=0
[2-81]= Cooling comfort setting.
Default value=1
Change [2-81]=0, 1, 2 or 3 in function of required
limitation.
This setting is used in conjunction with setting [2-8].
For more information and advice about the impact of
these settings, see "15.3. Energy saving and optimum
operation" on page 40.
Value
[2-31]
Power consumption limitation
(approximately)
1 40% (default)
250%
355%
Value
[2-32]
Restriction reference
0 Function not active (default)
1 Follows [2-30] setting
2 Follows [2-31] setting
Remark:
A combination of R410A and non-R410A VRV DX
indoor units cannot be used.
The list of compatible non-R410A indoor units is
restricted to the models mentioned in "3.2.1. Indoor
unit combinations" on page 3.
Value
[2-73]
Indoor unit type which can be used
0 R410A VRV DX indoor units
1 non-R410A VRV DX units
Value
[2-81]
Cooling comfort setting
0Eco
1 Mild (default)
2Quick
3 Powerful