Specifications

Installation and operation manual
48
RXYQQ8~20T7Y1B
VRV IV System Air Conditioner
4P345099-1 – 2013.04
4 Calculate the refrigerant density taking the volume of the room
where the indoor unit is installed and the adjacent room.
Install ventilation openings in the door of adjacent rooms until
the refrigerant density is smaller than the maximum
concentration level.
19. Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
20. Unit specifications
20.1. General technical specifications
INFORMATION
For technical and electrical details of multi unit
combinations, see technical engineering data.
RXYQQ8 RXYQQ10 RXYQQ12 RXYQQ14
Casing material Painted galvanised steel
Dimensions h x w x d
(mm)
1685x930x765
1685x1240
x765
Weight 187 194 305
Operation range
cooling (min./max.)
(°C)
–5/43
heating (min./max.)
(°C)
–20/21
Cooling
(a)
capacity
(kW)
22.4 28.0 33.5 40.0
•EER 4.30 3.84 3.73 3.64
Heating
(b)
capacity
(kW)
25.0 31.5 37.5 45.0
•COP 4.54 4.27 4.12 4.02
PED
category 2
Most critical part Accumulator
•PS*V
(bar*l)
325 415
Maximum number of indoor
units connected
(c)
64
Heat exchanger
•type cross fin
treatment anti corrosion
Fan
•type propeller
quantity 12
air flow rate
(d)
(m
3
/min)
162 175 185 223
motor 12
model brushless DC
output/pcs
(W)
750
Compressor
quantity 12
model inverter
•type hermetically sealed scroll compressor
crankcase heater
(W)
33
Sound level (nominal)
(e)
sound power
(f)
(dBA)
78 79 81
sound pressure
(g)
(dBA)
58 61
Refrigerant
•type R410A
charge (factory)
(kg)
5.9 6 6.3 10.3
Refrigerant oil Synthetic (ether) oil
Safety devices High pressure switch
Fan driver overload protector
Inverter overload protector
PC board fuse
(a) Nominal cooling capacities are based on indoor temperature 27°C DB and
19°C WB, outdoor temperature 35°C DB, equivalent refrigerant piping: 5 m, level
difference: 0 m.
(b) Nominal cooling capacities are based on indoor temperature 20°C DB, outdoor
temperature 7°C DB and 6°C WB, equivalent refrigerant piping: 5 m, level
difference: 0 m.
(c) Actual number of units depends on the connection ratio restriction for the system
(50%CR130%).
(d) Nominal at 230 V.
(e) Sound values are measured in a semi-anechoic room.
(f) Sound power level is an absolute value that a sound generates.
(g) Sound pressure level is a relative value depending on the distance and acoustic
environment. For more details, refer to sound level drawings in the technical data
book.
RXYQQ16 RXYQQ18 RXYQQ20
Casing material Painted galvanised steel
Dimensions h x w x d
(mm)
1685x1240x765
Weight 305 314
Operation range
cooling (min./max.)
(°C)
–5/43
heating (min./max.)
(°C)
–20/21
Cooling
(a)
capacity
(kW)
45.0 50.0 56.0
EER 3.46 3.40 3.03
Heating
(b)
capacity
(kW)
50.0 56.0 63.0
•COP 3.91 3.89 3.71
PED
category 2
Most critical part Accumulator
PS*V
(bar*l)
415 492.5
Maximum number of indoor
units connected
(c)
64
Heat exchanger
type cross fin
treatment anti corrosion
Fan
type propeller
quantity 2
air flow rate
(d)
(m
3
/min)
260 251 261
motor 2
model brushless DC
output/pcs
(W)
750
Compressor
quantity 2
model inverter
type hermetically sealed scroll
compressor
crankcase heater
(W)
33
Sound level (nominal)
(e)
sound power
(f)
(dBA)
86 88
sound pressure
(g)
(dBA)
64 65 66
Refrigerant
type R410A
charge (factory) 10.4 11.7 11.8
Refrigerant oil Synthetic (ether) oil
Safety devices High pressure switch
Fan driver overload protector
Inverter overload protector
PC board fuse
RXYQQ8 RXYQQ10 RXYQQ12 RXYQQ14