Specifications
SiBE34-703 Field Setting
Test Operation 89
The numbers in the "No." column represent the number of times to press the SET (BS2) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
1
Cool / Heat
Unified address
8777778
Address 0
8777777
∗
Binary number 1
8777778
(6 digits) ~
31
8788888
2
Low noise/demand
address
8777787
Address 0
8777777
∗
Binary number 1
8777778
(6 digits) ~
31
8788888
3 Test operation
8777788
Test operation : OFF
8777778
Test operation : ON
8777787
∗
5 Indoor forced fan H
8777878
Normal operation
8777778
∗
Indoor forced fan H
8777787
6
Indoor forced
operation
8777887
Normal operation
8777778
∗
Indoor forced operation
8777787
8Te setting
8778777
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
9 Tc setting
8778778
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
10
Defrost changeover
setting
8778787
Quick defrost
8777877
Normal (factory setting)
8777787
∗
Slow defrost
8777778
12
External low noise/
demand setting
8778877
External low noise/demand:
NO
8777778
∗
External low noise/demand:
YES
8777787
13 Airnet address
8778878
Address 0
8777777
∗
Binary number 1
8777778
(6 digits) ~
63
8888888
16
Setting of hot water
heater
8787777
OFF
8777778
∗
ON
8777787
20
Additional refrigerant
charging operation
setting
8787877
Refrigerant charging: OFF
8777778
∗
Refrigerant charging: ON
8777787
21
Refrigerant recovery /
vacuuming mode
setting
8787878
Refrigerant recovery /
vacuuming: OFF
8777778
∗
Refrigerant recovery /
vacuuming: ON
8777787
22
Night-time low noise
setting
8787887
OFF
8777777
∗
Level 1 (outdoor fan with 6 step or lower)
8777778
Level 2 (outdoor fan with 5 step or lower)
8777787
Level 3 (outdoor fan with 4 step or lower)
8777788