Specifications
Field Setting SiBE34-703
90 Test Operation
The numbers in the "No." column represent the number of times to press the SET (BS2) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
25 Low noise setting
8788778
Level 1 (outdoor fan with 6 step or lower)
8777778
Level 2 (outdoor fan with 5 step or lower)
8777787
∗
Level 3 (outdoor fan with 4 step or lower)
8777877
26
Night-time low noise
operation start
setting
8788787
About 20:00
8777778
About 22:00 (factory setting)
8777787
∗
About 24:00
8777877
27
Night-time low noise
operation end setting
8788788
About 6:00
8777778
About 7:00
8777787
About 8:00 (factory setting)
8777877
∗
28
Power transistor
check mode
8788877
OFF
8777778
∗
ON
8777787
29
Capacity
precedence setting
8788878
OFF
8777778
∗
ON
8777787
30 Demand setting 1
8788887
60 % demand
8777778
70 % demand
8777787
∗
80 % demand
8777877
32
Normal demand
setting
8877777
OFF
8777778
∗
ON
8777787