Specifications

Service Check Function SiUS12-928_A
99 Service Diagnosis
5. Press the TEMP or button and change the figure until you hear the beep.
6. Diagnose by the sound.
beep : The left digit does not correspond with the error code.
beep beep : The left digit corresponds with the error code but the right-side digit does not.
“long beep” : Both digits correspond with the error code.
7. Determine the error code.
The figures indicated when you hear the beepare error codes.
(Error codes and description
Refer to page 100.)
8. Press the MODE button to exit from the diagnosis mode.
The display “ ” means the trial operation mode.
(Refer to page 217 for trial operation.)
9. Press the ON/OFF button twice to return to the normal mode.
Note: When the remote controller is left untouched for 60 seconds, it returns to the normal mode.
(R4277)
(R4278)
(R9669)