5.15 Four-Way Valve Abnormality (18 Class)
Remote
Controller
Display
EA
Outdoor Unit LED
Display
A 5 1 4 2 1 3 1 4 1
Method of
Malfunction
Detection
The liquid pipe thermistor, the outdoor temperature thermistor and the outdoor heat exchanger
thermistor are checked to see if they function within their normal ranges in the operating mode.
Malfunction
Decision
Conditions
Either of the following conditions occurs 6 minutes after the compressor has started.
Cooling operation
Lowest temperature among the running indoor heat exchangers > 5°C (41°F)
Heating operation
Highest temperature among the running indoor heat exchangers < 0°C (32°F)
Supposed
Causes
Poor connector contact
Defective thermistor
Defective outdoor unit PCB
Defective four-way valve coil or harness
Defective four-way valve
Foreign substance mixed in refrigerant